Specifications/ambient conditions
Type
Capacity in l/h
at 7 bar
water pressure
Type
Capacity in l/h
at 7 bar
water pressure
Scope of versions in terms of capacity
CD ZE / DZ 20
CD ZE / DZ 40
CD ZE / DZ 60
CD ZE / DZ 80
CD ZE / DZ 100
CD ZE / DZ 120
CD ZE / DZ 160
CD ZE / DZ 200
20
40
60
80
100
120
160
200
CD ZE / DZ 300
CD ZE / DZ 400
CD ZE / DZ 500
CD ZE / DZ 750
CD ZE / DZ 1000
300
400
500
750
1000
Power consumption
(with booster pump)
155 VA
335 VA
Maximum acoustic power level
54 dBA
Mains supply (to control unit)
200…240 VAC/50…60 Hz
Voltage of solenoid valves (Y5-Y8)
24 VDC extra-low safety voltage
Number of steps (humidity control)
3-step (7-step with option
Z407
)
Resolution of humidity control
33% (14.2% with option
Z407
)
Control accuracy
1)
3-step: ±10% / 7-step (option
Z407
): ±4%
Control signals
– active
0…20 VDC (phase-control), 0…10VDC, 0…8.25VDC, 1…5VDC,
0…5VDC, 0…1VDC, 0…20mA, 4…20mA
– passive
all potentiometric humidity sensors from 1…10 kΩ
Central unit
– Weight
18,5 kg (Z409: 39,0 kg)
22,7 kg (Z409: 43,2 kg)
– Dimensions HxWxD
951 x 693 x 220 mm
(Z409: 600 x 600 x 210 mm and 300 x 500 x 210 mm)
Ceramic plate sizes
6
Maximum air velocity in duct
2,5 m/s
(without booster) 4 m/s (with booster)
Max. admissible supply air temperature
50 °C (before humidifier)
Water supply
– connector
– pressure
– water temperature
– water quality requirements
1/2" (outside thread), nominal width 15 mm
working pressure 2…10 bar
max. 45°C
fully demineralized water from reverse osmosis system with 0.5...15 µS/cm
(
without any additives
), max. 100 cfu/ml
Water drain connector (drain valve)
hose stem, outer ø16 mm or G 1/2" outside thread (Z409)
Water connector of humidifier
plug-in system (ø10 mm)
Nozzle pressure
4…10 bar
Nozzle sizes
4 (2.46 l/h, 3.10 l/h, 4.0 l/h, 5.0 l/h)
Monitoring of fully demineralized water
min. pressure, max. pressure, conductance, temperature of booster pump
Admissible ambient temperature
2)
1...40 °C
Admissible ambient humidity
2)
max. 75 %rh non-condensing
Test and conformity certificates
CE label
Schutzart
– control
– central unit
– central unit in protective cabinet (Z409)
IP 31
IP 30
IP 54
Options
remote operating and fault indication “Z401” or “Z401S” (wire breakage safe),
RS 232/485 interface “Z404”/“Z405”,
casing central unit “Z408”, central unit in protective cabinet “Z409”
1)
The nominal control accuracy may not always be available, because various factors (temperature control, water recy-
cling, flap valve systems, etc.) may affect the accuracy.
2)