27
13. Mounting the brackets for the upper flow sheets:
Starting with the narrow vertical section (left or right), align the front
edge of the first bracket with the front edge of the topmost opening in
the vertical section (see figure above), then fix the bracket to the duct
roof using 2 (or 3, as required) selftapping screws (drill holes ø3.3 mm
before). Mount the remaining brackets in an offset order (front/rear, see
figure above).
Important!
Mount the bracket marked with a “
V
” between the vertical
sections with systemspecific width.
14. Fix self-adhesive sealing plates to the two remaining angle brackets (see
illustration above). Use the M6x12 hexagon socket screws provided to
fix the angle brackets to the lower end of the two middle vertical sec
-
tions. Push angle brackets down to the duct floor, then fasten M6x12
hexagon socket screws. Now fix the angle brackets to the duct floor
using two selftapping screws provided (drill holes ø3.3 mm before).
Important!
Depending on the slope of the tub the angle brackets may
need to be fixed to the vertical sections using the extensions provided
(see enlarged section in the figure above).
V
13
V
ø3.3 mm
14
ø3.3 mm
ø3.3 mm