6
Fault elimination
6.1
Fault indication
Malfunctions during operation are indicated by a corresponding
Warning
or
Fault
message in the
display of the control unit (each warning and fault message is stored in the error list):
–
Warning messages
(additionally to the warning message the
red LED flashes
)
Further operation is still possible. The control of the Condair GS/Condair GS...OC checks whether
there is a temporary problem (e.g. gas supply interrupted for a short time) or whether it can re-
solve the problem by taking necessary measures. If the cause of the malfunction disappears of
its own accord or if the control can repair the malfunction, the alarm message will automatically
switch off. If the cause of the malfunction does not disappear even after a longer period of time,
a fault message is triggered.
–
Fault message
(additionally to the fault message the
red LED lights
)
Further operation is not possible any longer, the unit is blocked. To eliminate the malfunction see
chapter 6..
Note: After eliminating the malfunction the fault message must be reset (see chapter 6.4).
By pressing the
<Info>
key additional information can be displayed for each warning and/or fault
message.
Menu
Info
Warning
IMW-1:Ignition Module
Menu
Info
Fault
OTF: Over Temperature
Lockout
OTF: Over Temperature
safety sensor has
exceeded the safety
limit. Check water
The exhaust or tank
level, venting for
obstructions
Esc