Warning message

Description of malfunction

Trouble shooting

BLW-X: Blower RPM low

The speed of blower X has been lower 

than the speed of the leading blower for 

more than five seconds.

Corrective action by unit

: the unit con-

tinues to monitor the blower speed

1.  Make sure blower in question is cor-

rectly  connected  and  it  is  receiving 

correct voltage.

.  Check operation of blowers in the diag-

nostic output test for abnormalities.

.  Set blower in question as lead blower 

and see if other blowers get Blower 

High Warning.

4.  Blower  speed  is  decreasing  due  to 

wear. Unit is safe to operate but output 

is reduced.

5.  Order new blower.

HMW: Service due

The maintenance interval time has 

elapsed.

Corrective action by unit

: the unit will 

continue to run for 7 hours before a fault 

is generated

Service the unit according the maintenance 

instructions.

FTW: Fill timeout

The  fill  valve  has  been  activated  for  a 

certain period of time but the the unit is 

still at float level zero.

Corrective action by unit

: fill valve re-

mains activated. A fault message is trig-

gered if the float level remains at zero after 

next time window.

1.  Make sure that drain pump, auxiliary 

drain valve or manual drain switch are 

not activated.

.  Make sure that the water supply line is 

open and the water supply meets the 

requirements (10 L/min ; -8bar).

.  Check fill valve using the diagnostic 

output test.

4.  Check wiring to float board and fill 

valve.

5.  Clean water assembly of the unit.

RHHW: RH to high

The measured relative humidity is

higher than the “RH high” setting.

Corrective  action  by  unit

:  none.  The 

humidifier remains in standby mode until 

the  measured  relative  humidity  drops 

below setpoint.

1.  Check that “RH high” setting is correct 

for the application.

.  Make sure sensor is not influenced by 

other sources of humidity (wash basin, 

Sink, etc.).

.  Check the location of sensor (too close 

to steam distributor?)

4.  System might be oversized. Try to limit 

capacity of the unit.

RHLW: RH to low

The measured relative humidity is

lower than the “RH low” setting. 

Corrective  action  by  unit

:  none.  The 

humidifier should be operating unless it 

is in standby or lockout mode.

1.  Check that “RH low” setting is correct 

for the application.

.  Is  humidifier  in  lockout  or  standby? 

Investigate why humidifier is not op-

erational.

.  Check that sensor is not near a door 

or window or in any location that may 

give a false reading

4.  System could be undersized. Check 

power limit settings.

5.  Check  that  all  burners  are  opera-

tional.

RHW: RH signal defect

The RH signal input is lower than %

Corrective action by unit

: the operation 

is interrupted until an

input signal higher than % is received.

1.  Check connection between sensor and 

unit.

.  Check that sensor is functional

.  Check control settings of the unit.

4.  Make sure controls are located such 

that they provide accurate readings.

Содержание Control GS OC-C Series

Страница 1: ...operating instructions 1119124 EN 1005 Control Condair GS GS OC C series Gasfired steam humidifier...

Страница 2: ......

Страница 3: ...g the limit range in rh for the supply air limitation 19 4 1 3 11 6 Setting the damping time for the limit signal in seconds 20 4 1 3 11 7 Switching on and off the humidity alert function 20 4 1 3 11...

Страница 4: ...yright Act Passing on and reproduc tion of the manual or part thereof as well as exploitation and communication of the contents are prohibited without written permission by the manufacturer Violation...

Страница 5: ...LED if the external safety chain ventilation interlock has triggered is open As soon as the safety chain is closed again the indica tion disappears yellow LED Maintenance Function The LED lights if th...

Страница 6: ...display first page of the indication level Note The contents of the standard operating display depends on the ac tual operating status and on the configuration of the Condair GS Condair GS OC and can...

Страница 7: ...al 0 10V Modbus Addr 1 Menu Condair GS 240 Power Limit 100 Sys Request 50 Out Burner 30kg hr Total Steam 120kg hr Menu Condair GS 240 Burners 6 Active 4 Lead Buner 1 Disabled Menu Condair GS 240 Servi...

Страница 8: ...nfo page 2 Control Settings Menu Condair GS 240 Software 1 00LA00 Controlsign 0 10V Limitsignal 0 10V Modbus Addr 1 Software version 1 00 language version LA00 Set control signal range signal Y Set co...

Страница 9: ...operation Set draining rate per hour in of the maximum steam capacity related to 100 steam production Actual status of full tank draining On Tank is fully drained an refilled after the set operation t...

Страница 10: ...11 Actual status of the external safety circuit 12 Actual status of the temperature switch of the keep warm function 13 Actual status of the float check function 14 Actual status of the time proporti...

Страница 11: ...key several times to quit the malfunction history list and to return to the standard operating display The warning or error messages generated by the last 20 malfunctions that occurred are saved in a...

Страница 12: ...ry list and to return to the standard operating display Each time the maintencance message is reset an entry is automatically generated in the maintenace history list The last 20 entries are saved in...

Страница 13: ...selected dialogue language Factory setting country specific Options divers languages Select Language in the unit settings menu then press the Set key Time 12 00 Contrast 3 Unit Steam kg hr User Setti...

Страница 14: ...d regulation mode Factory setting External Options External external continuous controller 24VOn Off external On Off humidistat Int P Internal P controller Int PI Internal PI controller Esc Set Contro...

Страница 15: ...1 3 2 Select Controlsign in the control settings menu then press the Set key In the upcoming modification dialogue select the desired control signal Factory setting 0 10V Options 0 5V 1 5V 0 10V 2 10...

Страница 16: ...me Note This setting is available only if the short cycle delay Short CD function is activated see chapter 4 1 3 7 Select CD Time in the control settings menu then press the Set key In the upcoming mo...

Страница 17: ...to Master or Extension see chapter 4 1 3 4 Select MultiModeOp in the control settings menu then press the Set key Then Select Full Out to set the upper output limit or select Zero Out to set the lower...

Страница 18: ...odification dialogue set the desired proportional range in for the internal P PI controller Factory setting 15 Setting range 6 65 Esc Set Internal Settings P Band 15 Integr Time 5 Lim Setpoint 80 HumS...

Страница 19: ...n press the Set key In the upcoming modification dialogue set the desired limit range value in rh for the supply air limitation Factory setting 15 rh Setting range 6 20 rh Esc Set Control Integral Tim...

Страница 20: ...desired upper humidity alarm value for tirggering a humidity alert Factory setting 75 rH Options 20 95 rH Esc Set Limit Damping 5 s 5 s Internal Settings Limit Band 15 Lim Damp 5 RH Alerts On Lim Setp...

Страница 21: ...ndividual settings and press the Set key to call up the modification dialogue for the selected setting Please refer to the following chapters for further information on the individual water management...

Страница 22: ...setting 25 Setting range 1 50 4 1 5 3 Switching on and off full tank draining function If the full tank draining function is activated the tank is automatically drained after certain time see chapter...

Страница 23: ...6 Setting the idle mode Select Idle Mode in the water management menu then press the Set key In the upcoming modification dialogue set the desired idle mode Factory setting Idle Drain Setting range Id...

Страница 24: ...e drain rate Note Adjustments must only be made by factory trained personnel Select Drain Corr in the water management menu then press the Set key In the upcoming modification dialogue set the drain c...

Страница 25: ...settings menu then press the Set key The list with the remote relay tests appears Press the and keys in order to select the de sired relay test and press the Set key to activate deactivate the corres...

Страница 26: ...play contrast Factory setting 3 Setting range 0 weak 10 display turns black Esc Set Time 12 12 12 12 Settings Remote Test Set Date 01 10 08 Time 12 12 Water Mngm Set Unit Steam kg hr Contrast 3 Esc Se...

Страница 27: ...key In the upcoming modification dialogue select the desired Modbus adress bit for the unit Factory setting 1 Setting range 1 247 4 2 2 Setting the parity Select Parity in the Modbus settings menu th...

Страница 28: ...Disable in the Modbus settings menu then press the Set key In the upcoming modification dialogue you can switch On remote disabling activated or Off remote disabling activated the remote disabling fun...

Страница 29: ...s the Set key In the upcoming modification dialogue set the desired maintenance interval time in hours Factory setting 500 h Options 100 3000 h User Settings Set ModBus Set Maintenance Set Esc Set Mai...

Страница 30: ...water Upon completion of the fill cycle the tank is drained once again This removes any accumulated minerals and cools down the tank for maintenance Select TankPreClean in the maintenance settings me...

Страница 31: ...to find the cause of a malfunction Therefore use the error history reset function carefully Select ErrorHistory in the maintenance settings menu then press the Set key The reset dialogue shows up in t...

Страница 32: ...d or if the control can repair the malfunction the alarm message will automatically switch off If the cause of the malfunction does not disappear even after a longer period of time a fault message is...

Страница 33: ...put test on blower RPM to verify that air proving switches remain closed during opera tion 5 If air proving switch does not close during operation it might need to be replaced AOW X Air Proving open T...

Страница 34: ...in 3 8bar 3 Check fill valve using the diagnostic output test 4 Check wiring to float board and fill valve 5 Clean water assembly of the unit RHHW RH to high The measured relative humidity is higher t...

Страница 35: ...ectionbetweenmasterand extension unit RDW Modbus disable The unit has been intentionally disabled through the Building Management Sys tem Corrective action by unit none The unit was intentionally disa...

Страница 36: ...ving switch does not close during operation it might need to be replaced ACF X Airproving closed The corresponding air proving switch was closed while the blowers were inactive The unit will remain in...

Страница 37: ...r is con nectedandlevelschangeduringdrain ing FIF Fill inconsistent On startup the unit registers that the float levelsdonotincreaselogicallyfromlevel1 to level 5 The unit cannot operate without accur...

Страница 38: ...components may result Flash R W CPU can t write or read any data on the CPU Check if battery is low or CPU board is defective Clock R W CPU can t get any clock data Check if battery is low or CPU boar...

Страница 39: ...Walter Meier Climate International Ltd 2009 Printed in Switzerland Technical modifications reserved...

Страница 40: ...er Climate International Ltd Talstr 35 37 P O Box CH 8808 Pf ffikon Switzerland Phone 41 55 416 61 11 Fax 41 55 416 62 62 www waltermeier com international climate waltermeier com Solutions for Indoor...

Отзывы: