17
Controls
Unit Type :Set
Controlsign.:0-10V
Short CD :Off
Mod Mode :Single
Time Prop. :Off
MultiModeOp :set
4.1.3.9 Switching on and off the time proportioning function
The time proportioning function allows to produce steam below 5% system request (or less than
10kg/h) with an ON/OFF control.
Select “
Time Prop
” in the control settings menu, then press the
<Set>
key.
In the upcoming modification dialogue you can switch on or off the time proportioning function.
Factory setting:
Off
Options:
Off (no steam is produced below 25 % system request), On
4.1.3.10 Setting operating range for multiple units operation
Note: This setting is available only if the unit type is set to Master or Extension (see chapter 4.1..4).
Select “
MultiModeOp
” in the control settings menu, then press the
<Set>
key. Then, Select “
Full
Out.
” to set the upper output limit or select “
Zero Out.
” to set the lower output limit, then press the
<Set>
key.
In the upcoming modification dialogue set the upper or lower limit for the operating range of the
corresponding unit.
Controls
Mod Mode :Single
Unit Type :Set
Controlsign.:0-10V
Reg Mode :External
Short CD :Off
Time Prop. :Off
Esc
Set
Esc
Set
Time Proportioning
Off
On
Off
Esc
Set
Esc
Set
Full Out.
100 %
100 %
Esc
Set
Op. Range
Zero Out. : 0
Full Out. :100
Esc
Set
Zero Out.
0 %
0 %
Op. Range
Zero Out. : 0
Full Out. :100
Esc
Set
Settings
Controls :Set
Power Limit :100
Water Mngm. :Set
Language :English
Remote Test :Set
Date :01.10.08
Esc
Set
Settings
Controls :Set
Power Limit :100
Water Mngm. :Set
Language :English
Remote Test :Set
Date :01.10.08
Esc
Set