16
4.1.3.6 Selecting the limit signal
Note: This setting is available only if the internal P or PI controller or external (continuous) control-
ler is activated and the modulation mode (Mode Mode) is set to “Dual” (see chapters 4.1.. and
4.1..).
Select “
Limitsign.
” in the control settings menu, then press the
<Set>
key.
In the upcoming modification dialogue select the desired limit signal.
Factory setting:
0–10V
Options:
0–5V
,
1–5V
,
0–10V
,
2–10V
,
0–16V
,
3.2–16V
,
0–20mA
,
4–20mA
4.1.3.7 Switching on and off the short cycle delay function
The short cycle delay function reduces the number of ON/OFF cycles by forcing the system to wait
for a set time before responding to a demand.
Select “
Short CD
” in the control settings menu, then press the
<Set>
key.
In the upcoming modification dialogue you can switch on or off the short cycle delay function.
Factory setting:
Off
Options:
Off, On
4.1.3.8 Setting the short cycle delay time
Note: This setting is available only if the short cycle delay (Short CD) function is activated (see
chapter 4.1..7).
Select “
CD Time
” in the control settings menu, then press the
<Set>
key.
In the upcoming modification dialogue select the desired short cycle delay time.
Factory setting:
300 seconds
Setting range:
1 ... 2000 seconds
Esc
Set
Limit Signal
0-5V
1-5V
0-10V
0-10V
2-10V
0-16V
Controls
Mod Mode :Single
Unit Type :Set
Controlsign.:0-10V
Reg Mode :External
Short CD :Off
Time Prop. :Off
Esc
Set
Esc
Set
Short Cycle Delay
Off
On
Off
Controls
Unit Type :Set
Controlsign.:0-10V
Short CD :Off
Mod Mode :Single
CD Time :300
Time Prop. :Off
Esc
Set
Esc
Set
Short CycleDelay Time
300 s
300 s
Settings
Controls :Set
Power Limit :100
Water Mngm. :Set
Language :English
Remote Test :Set
Date :01.10.08
Esc
Set
Settings
Controls :Set
Power Limit :100
Water Mngm. :Set
Language :English
Remote Test :Set
Date :01.10.08
Esc
Set
Settings
Controls :Set
Power Limit :100
Water Mngm. :Set
Language :English
Remote Test :Set
Date :01.10.08
Esc
Set
Controls
Unit Type :Set
Controlsign.:0-10V
Limitsignal :0-10V
Mod Mode :Dual
Short CD :Off
Time Prop. :On
Esc
Set