19
4.1.3.11.3 Setting the integral time in minutes for the internal PI controller
Note: This setting is available only if the internal PI controller is activated (see chapter 4.1..).
Select “
Integr. Time
” in the internal control settings menu, then press the
<Set>
key.
In the upcoming modification dialogue set the desired integral time in minutes for the internal PI
controller.
Factory setting:
5 minutes
Setting range:
1...60 minutes
4.1.3.11.4 Setting the upper limit value in %rh for the supply air limitation
Note: This setting is available only if the modulation mode is set to “Dual” (see chapter 4.1..).
Select “
Lim.Setpoint
” in the internal control settings menu, then press the
<Set>
key.
In the upcoming modification dialogue set the desired upper limit value in %rh for the supply air
limitation.
Factory setting:
80 %rh
Setting range:
15 ... 95 %rh
4.1.3.11.5 Setting the limit range in %rh for the supply air limitation
Note: This setting is available only if the modulation mode is set to “Dual” (see chapter 4.1..).
Select “
Limit-Band
” in the internal control settings menu, then press the
<Set>
key.
In the upcoming modification dialogue set the desired limit range value in %rh for the supply air
limitation.
Factory setting:
15 %rh
Setting range:
6 ... 20 %rh
Esc
Set
Control Integral Time
5 min
5 min
Internal Settings
P-Band :15
Integr. Time:5
Lim.Setpoint:80
HumSetPoint :40
Limit-Band :15
Lim-Damp :5
Esc
Set
Esc
Set
Limit Set Point
80 %rH
80 %rH
Internal Settings
Integr. Time:5
Lim.Setpoint:80
Limit-Band :15
P-Band :15
Lim-Damp :5
RH Alerts :On
Esc
Set
Controls
Controlsign.:0-10V
Limitsignal :0-10V
Short CD :Off
Unit Type :Set
Time Prop. :Off
Int.Settings:Set
Esc
Set
Settings
Controls :Set
Power Limit :100
Water Mngm. :Set
Language :English
Remote Test :Set
Date :01.10.08
Esc
Set
Controls
Controlsign.:0-10V
Limitsignal :0-10V
Short CD :Off
Unit Type :Set
Time Prop. :Off
Int.Settings:Set
Esc
Set
Settings
Controls :Set
Power Limit :100
Water Mngm. :Set
Language :English
Remote Test :Set
Date :01.10.08
Esc
Set
Esc
Set
Limit-Band
15 %rH
15 %rH
Internal Settings
Lim.Setpoint:80
Limit-Band :15
Lim-Damp :5
Integr. Time:5
RH Alerts :On
RH High :75
Esc
Set
Controls
Controlsign.:0-10V
Limitsignal :0-10V
Short CD :Off
Unit Type :Set
Time Prop. :Off
Int.Settings:Set
Esc
Set
Settings
Controls :Set
Power Limit :100
Water Mngm. :Set
Language :English
Remote Test :Set
Date :01.10.08
Esc
Set