14
4.1.3 Control settings
Select “
Controls
” in the unit settings menu, then press the
<Set>
key.
The display with control settings appears. The settings available depend on the selected signal
source, the regulation mode and the modulation mode. The display above shows the maximum
number of settings available. Please refer to the following chapters for further information on the
individual control settings.
4.1.3.1 Selecting the singal source
Select “
Source
” in the control settings menu, then press the
<Set>
key.
In the upcoming modification dialogue select the desired signal source.
Factory setting:
Analog
Options:
Analog (internal or external controller)
,
Modbus
4.1.3.2 Selecting the regulation mode
Select “
Reg Mode
” in the control settings menu, then press the
<Set>
key.
In the upcoming modification dialogue select the desired regulation mode.
Factory setting:
External
Options:
External
(external continuous controller)
24VOn/Off
(external On/Off humidistat)
Int. (P)
(Internal P controller)
Int. (PI)
(Internal PI controller)
Esc
Set
Controls
Reg Mode :External
Mod Mode :Single
Unit Type :Set
Source :Analog
Controlsign.:0-10V
Short CD :Off
Esc
Set
Source
Analog
Modbus
Analog
Controls
Reg Mode :External
Mod Mode :Single
Unit Type :Set
Source :Analog
Controlsign.:0-10V
Short CD :Off
Esc
Set
Esc
Set
Regulation Mode
External
24On/Off
Int. (P)
External
Int. (PI)
Settings
Controls :Set
Power Limit :100
Water Mngm. :Set
Language :English
Remote Test :Set
Date :01.10.08
Esc
Set
Settings
Controls :Set
Power Limit :100
Water Mngm. :Set
Language :English
Remote Test :Set
Date :01.10.08
Esc
Set
Short CD :On
Time Prop. :On
CD Time :300
Esc
Set
Controls
Reg Mode :Int.(PI)
Mod Mode :Dual
Unit Type :Set
Source :Analog
Controlsign.:0-10V
Limitsignal :0-10V
MultiModeOp :Set
Int.Settings:Set
Settings
Controls :Set
Power Limit :100
Water Mngm. :Set
Language :English
Remote Test :Set
Date :01.10.08
Esc
Set