protection
The unse of s thermal magnetic circuit breaker is recommended for each
CF 1200
Spot
.
A good earth connection is essential for the correct operation of the fixture. Strict
adherance to regulatory norms is strongly recommended.
ATTENTION!, DANGER!
The electronic ballast with which the
CF 1200 Spot
is fitted, as with other electro-
nic devices, requires a correct dimension for the neutral conductor, since the current
in the neutral conductor is equal to the sum of the current in all the active conduc-
tors.
For example, if at the mains outlet a current of 10Amps is on phase R, 10Amps on
phase S, and 10Amps on phase T, a total current of 30 Amps exists in the netural.
Please note the above to ensure the correct selection of cable dimensions. Qualified
electrical personnel should always be consulted.
CF 1200 Spot
requires a proper earth connection to operate
safely and correctly. Never operate the fixture unless the
green/yellow conductor is connected
.