BASIC MENU 

  +   

(diagram C)

- Press simultaneously 

 + 

 during 5 seconds.

- By mean of 

 or 

 the values can be changed.

- Press   for validation.

- The parameters sequence is:

it

TYPE

SYSTEM REACTION

FAC-

TORY 

SET-

TING

1 BAR

P

We can select the pressure units 

displayed beetween bar and psi. 

bar

2 rc0 rc2

Fast-cycling alarm:

- rc0: alarm unabled.

- rc1: activated, when hamme

-

ring is detected it is delayed 

the start in order to protect 

the pump.

- rc2: alarm is activated and 

the pump is stopped upon 

detection.

rc0

3

r.01 r.99

Only if fast-cycling alarm has 

been activated in the previous 

step (rc1). It can be choosed the 

maximum time period between 

3 consecutive starts that will be 

considered fast cycling (between 

1 sec. and 99 sec.)

5 se

-

conds

4 Sb0 Sb1

Stand-by mode activated (Sb1), 

for low power consumption, or 

unabled (Sb0).

Sb0

ADVANCED MENU  

 +   + 

- Press simultaneously 

+   + 

 during 5 seconds.

- By mean of 

 or 

 the values can be changed.

- Press   for validation.

- The parameters sequence is:

it

TYPE

SYSTEM REACTION

FAC-

TORY 

SET-

TING

1

nc

no

Select the operation MODE 

as a conventional pressu-

re switch (nc = normally 

closed) or reverse (no = 

normally open). *ver nota 3

nc

2

E00

E01/02

(Only T-Kit Switchmatic2). 

Select the operation mode 

Individual (E00) or Master/

Slave (E01/E02) in case of 

be assembled in groups of 

two pumps. 

E00

3

d.05

d.1

(Only T-Kit Switchmatic 2). 

Sets the minimum gap bet

-

ween Pstart 1 and Pstart 2 

and/or Pstop 1 and Pstop 2.

d.05

4

ct0

ct9

Sets a time delay between 

0 and 9 seconds to the start 

(is not available in synchro

-

nized operation mode).

ct0

5

dt0

dt9

Sets a time delay between 

0 and 9 seconds to the 

stop.

dt0

6

Ar0

Ar1

Activation of the automatic 

restore system ART (Ar1) o 

disable (Ar0).

Ar0

7

P0.0

Px.x

It allows setting a minimum 

operating pressure under 

which the device would 

determine dry-running 

operation. It is very usefull 

in the basic model T-Kit 

Switchmatic where there 

is no reading of current 

intensity drawn. See Note 2. 

 0 bar

0 psi

8

t05

t99

Set the time period bet

-

ween 5 and 99 seconds 

below the minimum ope

-

rating pressure that will be 

considered a dry-running 

operation.

20”

9

c10

c30

It allows setting a % of no

-

minal current above which 

the device will activate the 

overcurrent protection.

c20

10

rS0

rS1

If we change rS0 to rS1 and 

push ENTER default values 

are restored.

rS0

Remark 2: 

Basic T-Kit Switchmatic 1 can only detect dry-running 

operation through the minimum pressure. This means 

that plumber must determine the water column of the 

installation, the start pressure of the pump and place 

the minimum pressure below the start pressure.

It can also occur that pumping system is running out 

of its curve so that the pump is unable to provide the 

minimum pressure because the flow requirement is 

excessive. In this case T-Kit Switchmatic 1

 

would acti-

vate a false dry-running alarm.

If these concepts are not clear, it is preferable not 

configure this protection or install the T-Kit Swit

-

chmatic 2 with accurate and easy setting of dry-run 

detection.

Remark 3:

By choosing “no” (normally open) it will operate as 

an auxiliary pressure control element in the suction 

of the pump. It will restart when the suction pressure 

reaches the configured PStart.

Example: 

- PStop:  

 

0,9 bar

  - 

PStart:  1,2 

bar

  

Содержание T-Kit SWITCHMATIC 1

Страница 1: ...choc lectrique Rischio di scossa elettricha Stromsto gefahr Risk of damaging the pressure assemblies and or the plant Riesgo de da o al grupo de presi n o a la instalaci n Risque de dommage au groupe...

Страница 2: ...marcha y paros se activa este aviso Debe ser activado en el paso 2 del MENU BASICO rc1 Pulsador manual de rearme RESET 3 Modos de operaci n diferencial inversado y sincroni zado solo SW2 Panel de man...

Страница 3: ...ida Desde estado ON dispositivo OFF Desde estado OFF el dispositivo se mantiene en marcha hasta que es soltado el pulsador click Visualizamos Pstart durante 3 segundos 3 Entramos a la configuraci n de...

Страница 4: ...t0 5 dt0 dt9 Permite establecer un retardo entre 0 y 9 segundos a la desco nexi n dt0 6 Ar0 Ar1 Permite activar el sistema de rear mes peri dicos autom ticos ART Ar1 o desactivarlo Ar0 Ar0 7 P0 0 Px x...

Страница 5: ...ulsadores para indicar la presi n deseada 4 Presiona para validar Nota 5 La descalibraci n del sensor de presi n no debe ser algo normal Si ocurre de forma repetida contactar con el servicio t cnico A...

Страница 6: ...Must be activated in the step 2 of the BASIC MENU rc1 Manual start push button ENTER 3 operation modes differential reverse and synchroni zed only SW2 Control panel with 3 digit display LED indicator...

Страница 7: ...rea ching Pstop From any configuration MENU the parameter value is accepted HOLD DOWN From state ON unit OFF From state OFF the pump starts and keeps operating until the push button is released click...

Страница 8: ...operation mode ct0 5 dt0 dt9 Sets a time delay between 0 and 9 seconds to the stop dt0 6 Ar0 Ar1 Activation of the automatic restore system ART Ar1 o disable Ar0 Ar0 7 P0 0 Px x It allows setting a m...

Страница 9: ...mark 5 pressure sensor decalibration should not be a normal event If it is frequently repeated contact the technical service WARNINGS AND ALARMS COD DESCRIP TION SYSTEM REACTION A01 O DRY RUN NING Onl...

Страница 10: ...Il devra tre activ dans l tape 6 du MENU BASE cr1 Bouton de r armement manuel RESET 3 modes de fonctionnement diff rentiel inverse et synchronis uniquement pour le SW 2 Panneau de commandes et afficha...

Страница 11: ...Sur ON dispositif OFF Sur OFF le dispositif reste en mar che jusqu ce que le bouton soit rel ch click Pstart appara t pendant 3 secondes 3 3 L cran de configuration de Pstart click Pstop appara t pend...

Страница 12: ...mode synchronis ct0 5 dt0 dt9 Permet de d finir un retard entre 0 et 9 secondes lors de la d connexion dt0 6 Ar0 Ar1 Permet d activer le syst me de r armement r gulier automatique ART Art ou de le d...

Страница 13: ...Ajustez les valeurs de la pression avec les touches et pour indiquer la pression correcte 4 Appuyer pour valider Remarque 5 l talonnage r p titif du capteur de pres sion n est pas une chose normale Si...

Страница 14: ...cono frequenti messe in marcia ed arresti si attiva questo avviso Deve essere attivato nel punto 2 del MENU BASE rc1 Pulsante manuale di riarmo RESET 3 tipi di operazioni diferenziale inversato e sinc...

Страница 15: ...ante nuta Da stato ON dispositivo OFF Da stato OFF il dispositivo rima ne in marcia fino che si rilascia il pulsante click Visualizziamo Pstart durante 3 secondi 3 Entriamo nella configurazione di Pst...

Страница 16: ...n ritardo tra 0 e 9 secondi alla sconnessione dt0 6 Ar0 Ar1 Permette attivare il sistema di riarmi periodici automatici ART Ar1 o desattivarli Ar0 Ar0 7 P0 0 Px x Permette di impostare una pressione m...

Страница 17: ...pressione desiderata 4 Premere per validare Nota 5 la staratura del sensore di pressione non deve essere una cosa normale Se accade di forma ripetuta contattare con il servizio tecnico AVVERTENZE ED...

Страница 18: ...hen ist und die Pumpe infolgedessen zu h ufig in Gang ge setzt und angehalten wird wird dieser Alarm ausgel st Die Funktion muss ber den Schritt 2 des GRUNDLE GENDEN MEN S aktiviert werden rc1 Druckta...

Страница 19: ...etzt sich in Gang und die Pumpe aktiviert sich bis Pstop Ausgehend von jedem beliebigen Konfigurationsmodus Validiert den eingegebenen Wert ge dr ckt halten Ausgehend vom Zustand ON Ger t auf OFF Ausg...

Страница 20: ...nstellung einer Einschaltverz gerung zwischen 0 und 9 Sekunden ct0 5 dt0 dt9 Erm glicht die Einstellung einer Ausschaltverz gerung zwis chen 0 und 9 Sekunden dt0 6 Ar0 Ar1 Erm glicht die Aktivierung d...

Страница 21: ...zeigt wird 4 Zur Validierung auf dr cken Hinweis 5 Im Normalfall sollte sich der Drucksensor nicht entkalibrieren Sollte dies dennoch h ufiger vorkommen so setzen Sie sich mit dem Kundendienst in Verb...

Страница 22: ...22 A...

Страница 23: ...23 T Kit SWITCHMATIC 2 T Kit SWITCHMATIC 1 B C D...

Страница 24: ...8 EN 60730 2 6 2008 UNE EN 60730 1 2003 A12 2004 A13 2005 A1 2005 A14 2007 CORRIG 2007 A15 2008 A16 2008 A2 2009 UNE EN 60730 2 6 2009 EN 61000 6 1 2007 A1 2012 EN 61000 6 3 2007 A1 2012 CE KONFORMIT...

Отзывы: