EXCELLENCE VERSION
Acoustic configuration: compressor soundproofing (SC)
General technical data - Performance
Size
260.6
280.6
300.6
320.6
340.6
360.6
400.8
440.8
480.8
Cooling
Cooling capacity
1
[kW]
736
794
856
909
965
1020
1148
1248
1356
Compressor power input
1
[kW]
213
230
244
262
279
297
325
363
396
Total power input
2
[kW]
231
248
269
287
304
322
358
394
430
Partial recovery heating capacity
3
[kW]
189,9
204,8
220,0
234,1
248,8
263,4
294,6
322,2
350,4
Total recovery heating capacity
3
[kW]
892,0
964,0
1035,0
1106,0
1178,0
1249,0
1407,6
1549,8
1692,0
EER
1
-
3,19
3,20
3,18
3,17
3,17
3,17
3,21
3,17
3,15
Water flow-rate (User Side)
1
[l/s]
34,9
37,6
40,6
43,1
45,7
48,4
54,4
59,2
64,3
Internal exchanger pressure drops
1
[kPa]
53,5
52,5
53,4
56,9
57,3
57,7
51,2
50,1
54,6
Cooling capacity (EN14511:2013)
4
[kW]
734
791
852
905
961
1016
1143
1242
1350
Total power input (EN14511:2013)
4
[kW]
236
253
274
292
309
328
362
400
435
EER (EN 14511:2013)
4
-
3,11
3,12
3,11
3,10
3,10
3,10
3,16
3,10
3,10
ESEER
4
-
4,51
4,54
4,52
4,51
4,50
4,50
4,47
4,46
4,52
Cooling capacity (AHRI 550/590)
5
[kW]
733
790
853
906
962
1017
1140
1240
1351
Total power input (AHRI 550/590)
5
[kW]
231
248
269
286
304
322
357
393
429
COP
R
5
-
3,17
3,19
3,17
3,17
3,16
3,16
3,19
3,16
3,15
IPLV
5
-
5,06
5,09
5,07
5,06
5,04
5,03
5,00
5,00
5,08
1. Data referred to the following conditions: internal exchanger water = 12/7 °C. Entering external exchanger air
temperature 35°C. Evaporator fouling factor = 0.44 x 10^(-4) m2 K/W
2. The Total Power Input value does not take into account the part related to the pumps and required to overcome
the pressure drops for the circulation of the solution inside the exchangers
3. Option. Recovery exchanger water=40/45°C
4. Data compliant to Standard EN 14511:2013 referred to the following conditions: - Internal exchanger water
temperature = 12/7°C - Entering external exchanger air temperature = 35°C
5. Data compliant to Standard AHRI 550/590 referred to the following conditions: internal exchanger water
temperature = 6,7 °C. Water flow-rate 0,043 l/s per kW. Entering external exchanger air temperature 35°C.
Evaporator fouling factor = 0.18 x 10^(-4) m
2
K/W
Acoustic configuration: super-silenced (EN)
General technical data - Performance
Size
260.6
280.6
300.6
320.6
340.6
360.6
400.8
440.8
480.8
Cooling
Cooling capacity
1
[kW]
707
758
822
871
922
972
1098
1198
1284
Compressor power input
1
[kW]
224
243
255
274
294
313
340
382
420
Total power input
2
[kW]
237
256
273
292
312
331
364
406
443
Partial recovery heating capacity
3
[kW]
186,1
200,3
215,5
229,0
243,0
257,1
287,6
316,0
340,8
Total recovery heating capacity
3
[kW]
892,0
964,0
1035,0
1106,0
1178,0
1249,0
1393,5
1526,0
1673,9
EER
1
-
2,98
2,96
3,01
2,98
2,95
2,94
3,02
2,95
2,90
Water flow-rate (User Side)
1
[l/s]
33,5
35,9
39,0
41,3
43,7
46,1
52,0
56,8
60,8
Internal exchanger pressure drops
1
[kPa]
49,5
48,2
49,6
52,6
52,7
52,7
47,0
46,2
49,2
Cooling capacity (EN14511:2013)
4
[kW]
704
756
819
868
918
969
1094
1194
1279
Total power input (EN14511:2013)
4
[kW]
241
261
278
297
317
336
367
409
448
EER (EN 14511:2013)
4
-
2,92
2,90
2,95
2,92
2,90
2,88
2,98
2,92
2,86
ESEER
4
-
4,47
4,46
4,50
4,48
4,46
4,45
4,39
4,43
4,43
Cooling capacity (AHRI 550/590)
5
[kW]
704
756
819
869
919
968
1082
1191
1280
Total power input (AHRI 550/590)
5
[kW]
236
256
273
291
311
330
365
405
442
COP
R
5
-
2,98
2,95
3,00
2,99
2,95
2,93
2,96
2,94
2,90
IPLV
5
-
4,99
5,01
5,06
5,02
4,99
4,96
4,92
4,96
4,97
1. Data referred to the following conditions: internal exchanger water = 12/7 °C. Entering external exchanger air
temperature 35°C. Evaporator fouling factor = 0.44 x 10^(-4) m2 K/W
2. The Total Power Input value does not take into account the part related to the pumps and required to overcome
the pressure drops for the circulation of the solution inside the exchangers
3. Option. Recovery exchanger water=40/45°C
4. Data compliant to Standard EN 14511:2013 referred to the following conditions: - Internal exchanger water
temperature = 12/7°C - Entering external exchanger air temperature = 35°C
5. Data compliant to Standard AHRI 550/590 referred to the following conditions: internal exchanger water
temperature = 6,7 °C. Water flow-rate 0,043 l/s per kW. Entering external exchanger air temperature 35°C.
Evaporator fouling factor = 0.18 x 10^(-4) m
2
K/W
M08T40D16-02
WSAT-XSC3 260.6-480.8
59
Содержание WSAT-XSC3 260.6-480.8
Страница 46: ...46 WSAT XSC3 260 6 480 8 M08T40D16 02 8 16 Compressor replacement ...
Страница 47: ...M08T40D16 02 WSAT XSC3 260 6 480 8 47 8 17 Exchanger replacement 8 18 Pump replacement ...
Страница 49: ...M08T40D16 02 WSAT XSC3 260 6 480 8 49 ...
Страница 50: ...50 WSAT XSC3 260 6 480 8 M08T40D16 02 ...
Страница 75: ...Page intentionally left blank M08T40D16 02 WSAT XSC3 260 6 480 8 75 ...