4.6 Hydraulic connections
UNIT
A
filettare –
to thread
saldare –
to weld
A1
A2
impianto -
system
A + B :
fornito da Clivet -
Clivet supplied
o -
or
B
A
Do not weld the system pipe with the Victaulic connection joint attached.
The rubber gasket might be irreparably damaged.
4.7 Recommended connection
The installer must define
•
component type
•
position in system
2
7
9
13
3
1
14
UNIT
6
10
12
4
5
8
15
F
11
1
antivibration joints
9
safety valve
2
piping support
10
Flow Switch
3
exchanger chemical cleaning bypass
11
pressure gauge
4
drain valve
12
thermometer
5
vent
13
filter
6
shut-off valve
14
Internal storage tank
7
Pump / circulating pump
15
Cleaning system bypass
8
expansion vessel
4.8 Water filter
Use fil er with mesh pitch:
1,6 mm
It must be installed immediately in the water input of the unit, in a position that is easily accessible for cleaning.
The fil er never should be removed, this operation invalidates the guaranty.