M08T40D16-02
WSAT-XSC3 260.6-480.8
41
8 Maintenance
8.1 General description
Maintenance must be done by authorized centres or by qualified personne .
The maintenance allows to:
•
maintain the unit efficie y
•
increase the life span of the equipment
•
assemble information and data to understand the state of the unit efficie y and avoid possible damages
Before checking, please verify the following:
•
the electrical power supply line should be isolated at the beginning
•
the unit isolator is open, locked and equipped with the suitable warning
•
make sure no tension is present
After turning off the p wer, wait at least 5 minutes before accessing to the electrical panel or any other electrical component.
Before accessing check with a multimeter that there are no residual stresses.
OFF
OFF
ON
!
STANDARD UNIT
8.2 Unit booklet
It’s advisable to create a unit booklet to take notes of the unit interventions.
In this way it will be easier to adequately note the various interventions and aid any troubleshooting.
Report on the booklet:
•
date
•
intervention description
•
carried out measures etc.
8.3 Standby mode
If a long period of inactivity is foreseen:
•
turn off the p wer
•
avoid the risk of frost (empty the system or add glycol)
Turn off the p wer to avoid electrical risks or damages by lightning strikes.
With lower temperatures keep heaters turned on in of the electrical panel (option).
It’s recommended that the re-start after the stopping period is performed by a qualified technician, especially after seasonal stops or seasonal
switching.
When restarting, refer to what is indicated in the “start-up” section.
Schedule technical assistance in advance to avoid hitches and to guarantee that the system can be used when required.
Содержание WSAT-XSC3 260.6-480.8
Страница 46: ...46 WSAT XSC3 260 6 480 8 M08T40D16 02 8 16 Compressor replacement ...
Страница 47: ...M08T40D16 02 WSAT XSC3 260 6 480 8 47 8 17 Exchanger replacement 8 18 Pump replacement ...
Страница 49: ...M08T40D16 02 WSAT XSC3 260 6 480 8 49 ...
Страница 50: ...50 WSAT XSC3 260 6 480 8 M08T40D16 02 ...
Страница 75: ...Page intentionally left blank M08T40D16 02 WSAT XSC3 260 6 480 8 75 ...