Admissible water flow-rates
Minimum (Qmin) and maximum (Qmax) admissible water fl w for the unit to operate correctly.
EXCELLENCE
260.6
280.6
300.6
320.6
340.6
360.6
400.8
440.8
480.8
Qmin
[l/s]
17,6
19,2
20,5
21,0
22,3
23,6
28,7
31,6
32,9
Qmax
[l/s]
48,9
53,2
56,8
58,3
61,6
64,8
77,2
84,8
87,9
PREMIUM
260.6
280.6
300.6
320.6
340.6
360.6
400.8
440.8
480.8
Qmin
[l/s]
15,2
16,6
17,6
19,2
19,7
21,0
25,6
28,7
31,6
Qmax
[l/s]
42,6
46,5
48,9
53,2
54,6
58,3
69,1
77,2
84,8
Overload and control device calibrations
open
closed
value
High pressure safety pressure switch
[kPa]
4050
3300
-
Antifreeze protection
[°C]
4
5.5
-
High pressure safety valve
[kPa]
-
-
4500
Low pressure safety valve
[kPa]
-
-
2950
Max no. of compressor starts per hour
[n°]
-
-
10
High compressor discharge temperature safety thermostat
[°C]
-
-
140
Exchanger operating range
Internal exchanger
DPr
DPw
PED (CE)
4500
4500
1000
DPr = Maximum operating pressure on refrigerant side in kPa
DPw = Maximum operating pressure on water side in kPa
M08T40D16-02
WSAT-XSC3 260.6-480.8
69
Содержание WSAT-XSC3 260.6-480.8
Страница 46: ...46 WSAT XSC3 260 6 480 8 M08T40D16 02 8 16 Compressor replacement ...
Страница 47: ...M08T40D16 02 WSAT XSC3 260 6 480 8 47 8 17 Exchanger replacement 8 18 Pump replacement ...
Страница 49: ...M08T40D16 02 WSAT XSC3 260 6 480 8 49 ...
Страница 50: ...50 WSAT XSC3 260 6 480 8 M08T40D16 02 ...
Страница 75: ...Page intentionally left blank M08T40D16 02 WSAT XSC3 260 6 480 8 75 ...