7.9 Keyboard settings
Step Display
Action
Menu/Variable
Keys
Notes
1
Press 3 sec.
2
Press
3
HMI Settings
Select
4
Press
5
Press
6
Select
Local connections
7.10 Alarms
Before resetting an alarm identify and remove its cause.
Repeated resets can cause irreversible damage.
Example:
+ eE0001: Phase monitor: Fault = active alarm
- EE0003: Pum 1 faulty: Ok = resetted alarm
Display of alarm: step 1-3
Reset allarm: step 4-10
Step Display
Action
Menu/Variable
Keys
Notes
1
Press
2
Alarm list detail
Press
3
Alarm list
Select
Alarm
4
Alarm list detail
Press 3 sec.
5
Password
Set
Enter password
6
Alarm list detail
Press
7
Alarm list
Select
Alarm
8
Select
Reset
Executed
9
Press 3 sec.
10
Password management
Select
Log off
For details see:
General list of alarms