8
WSAN-XES 18.2-35.2
M0SM40N17-04
3 POSITIONING
During positioning consider these elements :
technical spaces required for the machine and system
place where the machine will be installed
electrical connections
water connections
air / aeraulic ducts
FUNCTIONAL SPACES
Functional spaces are designed to:
guarantee good unit operation
Carry out maintenance operations
protect authorized operators and exposed people
Respect all functional spaces indicated in the
TECHNICAL INFORMATION section.
POSITIONING
Units are designed to be installed:
EXTERNAL
in fixed positions.
Limit vibration transmission:
use antivibration devices on unit bearing/supporting
points;
install flexible joints on the hydraulic.
Installation standards:
customer approval
safe accessible position
technical spaces requested by the unit
spaces for the air intake/exhaust
max. distance allowed by the electrical connections
install the unit raised from the ground
verify unit weight and bearing point capacity
verify that all bearing points are aligned and
leveled
condensate water draining
consider the maximum possible snow level
Avoid installations in places subject to flooding
Protect the unit with suitable fence in order to avoid
access to unauthorised personnel (children, vandals,
etc.)
A correct circulation of the air is mandatory to
guarantee the good unit operating.
A correct circulation of the air is indispensible to
guarantee the good working order of the machine.
Avoid therefore:
obstacles to the airflow
exchange difficulties
leaves or other foreign bodies that can obstruct
the exchange batteries;
winds that hinder or favour the airflow
heat or pollution sources close to the unit
(chimneys, extractors etc);
stratification (cold air that stagnates at the
bottom);
recirculation (expelled air that is sucked in
again);
positioning below the level of the threshold,
close to very high walls, attics or in angles that
could give rise to stratification or recirculation
phenomenons.
Stratification or recirculation
Ignoring the previous indications could
energy efficiency decrease
alarm lockout due to HIGH PRESSURE (in
summer) or LOW PRESSURE (in winter)
A
B
C
D
E
G
F
G
G
F
A = 800 mm
B = 500 mm
C = 800 mm
D = 500 mm
E = 6000
F = 500 mm
G = 500 mm
Содержание WSAN-XES 18.2
Страница 7: ...7 WSAN XES 18 2 35 2 M0SM40N17 04 ...
Страница 10: ...10 WSAN XES 18 2 35 2 M0SM40N17 04 Protection grilles Option PESM00007 PESM00008 ...
Страница 18: ...18 WSAN XES 18 2 35 2 M0SM40N17 04 Connections by the Customer ...
Страница 21: ...21 WSAN XES 18 2 35 2 M0SM40N17 04 UNITS IN MODULAR CONFIGURATION ...
Страница 48: ...48 WSAN XES 18 2 35 2 M0SM40N17 04 Exchanger replacement Pump replacement Compressor replacement ...