20
WSAN-XES 18.2-35.2
M0SM40N17-04
Addressing controls
A maximum of 16 controls can be addressed, with address from 0 to 15; so for example :
16 units with relative controller on board, one of which is the master
15 units with relative controller on board + a remote controller as the master
Press MENU + ► for 3 seconds
Press ▲▼ to select the address
REMOTE CONTROL
With S5_3 ON, the unit is controlled remotely.
Wired controller disabled
ON/OFF status: controlled by the On/Off input
input ON = unit ON
Heat/Cool mode : controlled by the Heat/Cool input
On = heating, Off = Cooling
With the units in modular configuration, remote control must be applied to the
master unit, which transmits it to the slave units.
After having set S5_3 disconnect and reconnect the power supply to confirm the
change.