24
WSAN-XES 18.2-35.2
M0SM40N17-04
Adress
Function
notes
247+(Address)*100
Outdoor air temperature - T4
1°C
248+(Address)*100
Compressor speed
1Hz
249+(Address)*100
Current of compressor 1
1A
250+(Address)*100
Fan 1 speed
Current speed
251+(Address)*100
Fan 2 speed
Current speed
252+(Address)*100
Fan 3 speed
Current speed
253+(Address)*100
EXVA
Current position
254+(Address)*100
EXVB
Current position
255+(Address)*100
EXVC
Current position
256+(Address)*100
SV4
0 Off, 1 On
257+(Address)*100
SV5
0 Off, 1 On
258+(Address)*100
SV8A
0 Off, 1 On
259+(Address)*100
SV8B
0 Off, 1 On
260+(Address)*100
4-way valve
0 Off, 1 On
261+(Address)*100
circulation pump
0 Off, 1 On
262+(Address)*100
SV1
0 Off, 1 On
263+(Address)*100
SV2
0 Off, 1 On
264+(Address)*100
HEAT1
0 Off, 1 On
265+(Address)*100
HEAT2
0 Off, 1 On
266+(Address)*100
compressor 1 discharge temperature - Tp1
1°C
267+(Address)*100
suction temperature - Th
1°C
268+(Address)*100
air coil temperature - T3
1°C
269+(Address)*100
liquid line temperature (in cooling) - Tz
1°C
270+(Address)*100
DHW storage temperature - T5
1°C
271+(Address)*100
P PRESSURE
10 kPa
272+(Address)*100
error / protection
see error codes table
273+(Address)*100
last error / protection
see error codes table
274+(Address)*100
software version
HMI
275+(Address)*100
compressor 2 discharge temperature - Tp2
1°C
276+(Address)*100
not used
277+(Address)*100
economizer inlet temperature - T6a
1°C
278+(Address)*100
wired control error
279+(Address)*100
SV6
0 Off, 1 On
280+(Address)*100
Compressor absorption 2
1A
Содержание WSAN-XES 18.2
Страница 7: ...7 WSAN XES 18 2 35 2 M0SM40N17 04 ...
Страница 10: ...10 WSAN XES 18 2 35 2 M0SM40N17 04 Protection grilles Option PESM00007 PESM00008 ...
Страница 18: ...18 WSAN XES 18 2 35 2 M0SM40N17 04 Connections by the Customer ...
Страница 21: ...21 WSAN XES 18 2 35 2 M0SM40N17 04 UNITS IN MODULAR CONFIGURATION ...
Страница 48: ...48 WSAN XES 18 2 35 2 M0SM40N17 04 Exchanger replacement Pump replacement Compressor replacement ...