19
WSAN-XES 18.2-35.2
M0SM40N17-04
UNITS IN MODULAR CONFIGURATION
Set the correct date and time on each unit before connecting them to the network
Enable multiple configuration:
SW12-2 :
ON units in multiple configuration
OFF single unit
The modular configuration consists of two networks, the controller network and the unit network (main boards).
Each network can have up to 16 addresses (from 0 to 15) and must be addressed separately.
Each network has its own master, which must have address 0
If some slaves have no DHW option:
configure as master a unit without DHW option.
assign the major addresses to the slaves equipped with DHW option
Addressing units in multiple configuration
They are addressed through the encoder ENC4 on the back of the
keypad.
The address corresponds to the encoder no.
The address is shown on the display DSP1.
MASTER : address = 0 encoder = 0
SLAVE 1 : address = 1 encoder = 1
SLAVE 15 : address = 15 encoder = F
The unit address is shown on the main board in the display called
"DSP1".