M0SM40N17-04
Error code
Description
troubleshooting
P6
module error
P7
condenser high temperature
P8
Reserved
P9
Inlet / outlet water temperature difference
If the protection intervenes 3 times in 60 minutes, turn the power
off to reset it.
PA
Reserved
Pb
winter antifreeze
PC
evaporator low pressure in cooling
Check the water flow rate.
PE
antifreeze protection evaporator low
temperature in cooling
If the protection intervenes 3 times in 60 minutes, turn the power
off to reset it.
Check that probe Two is correctly positioned.
PF
circuit board lock - controller lock/unlock error
PH
high room temperature probe T4
PL
Tfin module, high temperature
If the protection intervenes 3 times in 100 minutes, turn the
power off to reset it.
1PP
IPM module error, circuit A
2PP
IPM module error, circuit B
1PU
fan A module
2PU
fan B module
3PU
fan C module
1H9
driver compressor A - configuration error
2H9
driver compressor B - configuration error
H5
High / low voltage
1HE
valve A error
2HE
valve B error
3HE
valve C error
1F0
IPM module transmission error
2F0
IPM module transmission error
F2
insufficient overheating
If the protection intervenes 3 times in 240 minutes, turn the
power off to reset it.
1F3
Fan A transmission error
2F3
Fan B transmission error
3F3
Fan C transmission error
1F4
protection L0 or L1 intervention 3 times in 60
minutes
2F4
protection L0 or L1 intervention 3 times in 60
minutes
1F6
circuit A bus voltage (PTC)
2F6
circuit B bus voltage (PTC)
Содержание WSAN-XES 18.2
Страница 7: ...7 WSAN XES 18 2 35 2 M0SM40N17 04 ...
Страница 10: ...10 WSAN XES 18 2 35 2 M0SM40N17 04 Protection grilles Option PESM00007 PESM00008 ...
Страница 18: ...18 WSAN XES 18 2 35 2 M0SM40N17 04 Connections by the Customer ...
Страница 21: ...21 WSAN XES 18 2 35 2 M0SM40N17 04 UNITS IN MODULAR CONFIGURATION ...
Страница 48: ...48 WSAN XES 18 2 35 2 M0SM40N17 04 Exchanger replacement Pump replacement Compressor replacement ...