
42
WSAN-XES 18.2-35.2
M0SM40N17-04
Error code
Description
troubleshooting
F7
Reserved
1F9
radiator temperature sensor Tfin1
2F9
radiator temperature sensor Tfin2
1FA
Reserved
2FA
Reserved
Fb
pressure sensor
Detection begins 15 minutes after start-up, if a pressure
lower than 0.3 MPa is detected.
Not detected during defrosting.
Fd
suction temperature sensor
FE
recovery temperature sensor
1FF
fan A
2FF
fan B
3FF
fan C
FP
DIP switch for modular unit configuration error
C7
3 times PL
L0
module protection
L1
low voltage
L2
high voltage
L4
MCE error
L5
speed 0
L7
no phase
L8
variation of frequency higher than 15Hz
L9
difference of phase frequency higher than 15Hz
d0
Gate error (d0 and address alternatively
displayed every 10 sec)
dF
defrosting
Содержание WSAN-XES 18.2
Страница 7: ...7 WSAN XES 18 2 35 2 M0SM40N17 04 ...
Страница 10: ...10 WSAN XES 18 2 35 2 M0SM40N17 04 Protection grilles Option PESM00007 PESM00008 ...
Страница 18: ...18 WSAN XES 18 2 35 2 M0SM40N17 04 Connections by the Customer ...
Страница 21: ...21 WSAN XES 18 2 35 2 M0SM40N17 04 UNITS IN MODULAR CONFIGURATION ...
Страница 48: ...48 WSAN XES 18 2 35 2 M0SM40N17 04 Exchanger replacement Pump replacement Compressor replacement ...