23
WSAN-XES 18.2-35.2
M0SM40N17-04
Addresses 0 - 15 are the addresses of the selected units.
(addresses)*100+240—(addresses)*100+299 , are read only.
Units in modular configuration
Reading register
Adress
function
notes
240+(Address)*100
Running mode
1 shutdown
2 cooling
3 heating
241+(Address)*100
SILENT mode
1 Standard
2 Silent
3 Super silent
242+(Address)*100
Setpoint
1°C
243+(Address)*100
Setpoint B
1°C
244+(Address)*100
Unit inlet water temperature - Twi
1°C
245+(Address)*100
Unit outlet water temperature - Two
1°C
246+(Address)*100
Total outlet water temperature - Tw
1°C ; only for the master (0)
Address
function
notes
101
Double setpoint
Enable/Disable 1/0
102
1st setpoint in cooling
(
5~20
℃)
103
2nd setpoint in cooling
(
5~20
℃)
104
1st setpoint in heating
(
25~55
℃)
105
2nd setpoint in heating
(
25~55
℃)
106
temperature compensation in cooling
Enable/Disable
107
point 1 temperature compensation in cooling
25~30
℃
108
point 2 temperature compensation in cooling
35~40
℃
109
temperature compensation value in cooling
0~15
℃
110
temperature compensation in heating
Enable/Disable
111
point1 temperature compensation in heating
0~5
℃
112
point2 temperature compensation in heating
15~20
℃
113
temperature compensation value in heating
0~15
℃
138
Modbus write enable
1 = enabled; 0 = disabled
Reading and writing register
.
Содержание WSAN-XES 18.2
Страница 7: ...7 WSAN XES 18 2 35 2 M0SM40N17 04 ...
Страница 10: ...10 WSAN XES 18 2 35 2 M0SM40N17 04 Protection grilles Option PESM00007 PESM00008 ...
Страница 18: ...18 WSAN XES 18 2 35 2 M0SM40N17 04 Connections by the Customer ...
Страница 21: ...21 WSAN XES 18 2 35 2 M0SM40N17 04 UNITS IN MODULAR CONFIGURATION ...
Страница 48: ...48 WSAN XES 18 2 35 2 M0SM40N17 04 Exchanger replacement Pump replacement Compressor replacement ...