14
WSAN-XES 18.2-35.2
M0SM40N17-04
TW Probe
It must be installed on the supply of the unit, as far away as possible.
SINGLE UNIT: antifreeze function
MODULAR UNIT: thermoregulation (see diagram below)
water fittings for modular unit
water fittings for modular unit
UNIT IN MODULAR CONFIGURATION
Maximum 4 units in the same water branch.
Maximum total 16 units.
All units must be electrically connected to each other (see ELECTRICAL CONNECTIONS chapter)
Each module must be configured with the water fittings for modular unit (AMOD).
Each module can be equipped with inertial system storage tank (ACIMP).
Each unit with DHW option must have its own DHW storage tank.
It is not possible to have a hydronic assembly installed on board.
It is necessary to provide an external pumping unit, sized for the entire capacity of the modular system (responsibility of
the Customer).
The pumping unit will be managed by the Master unit through a potential-free contact and 0-10V signal.
See page 19 for the configuration.
Taf1
T5
Tw