8 MAINTENANCE
8.1 General
Maintenance must be done by authorized centres or by
qualified personnel
The maintenance allows to:
maintain the unit efficiency
reduce the deterioration speed to whom every
equipment is subject over time
assemble information and data to understand the
state of the unit efficiency and avoid possible
damages
Before checking, please verify the following:
the electrical power supply line should be isolated
at the beginning
the unit isolator is open, locked and equipped with
the suitable warning
make sure no tension is present
After turning off the power, wait at least 5 minutes
before accessing to the electrical panel or any other
electrical component.
Before accessing check with a multimeter that there
are no residual stresses.
8.2 Inspections frequenty
Perform an inspection every 6 months minimum.
The frequency, however, depends on the use.
In the event of frequent use it is recommended to plan
inspections at shorter intervals:
frequent use (continuous or very intermittent use,
near the operating limits, etc)
critical use (service necessary)
intervention frequency (months)
1
6
12
1
presence corrosion
X
2
panel fixing
X
3
fan fixing
X
4
coil cleaning
X
5
pulizia filtro acqua
X
6
water: quality, pH, glycol concentration
X
7
exchanger efficiency check
X
8
circulation pump
X
9
check of the fixing and the insulation of the power lead
X
10
check of the earthing cable
X
11
electric panel cleaning
X
12
power remote controls status
X
13
termina closing, cable insulation integrity
X
14
voltage and phase unbalancing (no load and on-load)
X
15
absorptions of the single electrical loads
X
16
compressor casing heaters test
X
17
Checking for leaks*
*
18
survey of the refrigerant circuit operating parameters
X
19
safety valve*
*
20
protective device test: pressure switches, thermostats, flow switches etc..
X
21
control system test: setpoint, climatic compensations, capacity stepping, water / air flow-rate
variations
X
22
control device test: alarm signalling, thermometers, probes, pressure gauges etc..
..
X
* Refer to the local regulations; and ensure correct adherance. Companies and technicians that effect interventions of
installation, maintenance/re-pairs, leak control and recovery must be CERTIFIED as expected by the local
regulations. The leak control must be effected with annual renewal.
Содержание WSAN-XES 18.2
Страница 7: ...7 WSAN XES 18 2 35 2 M0SM40N17 04 ...
Страница 10: ...10 WSAN XES 18 2 35 2 M0SM40N17 04 Protection grilles Option PESM00007 PESM00008 ...
Страница 18: ...18 WSAN XES 18 2 35 2 M0SM40N17 04 Connections by the Customer ...
Страница 21: ...21 WSAN XES 18 2 35 2 M0SM40N17 04 UNITS IN MODULAR CONFIGURATION ...
Страница 48: ...48 WSAN XES 18 2 35 2 M0SM40N17 04 Exchanger replacement Pump replacement Compressor replacement ...