Proprietary Information: Not for use or disclosure except by written agreement with Clearfield.
160
FieldSmart
®
Fiber Active Cabinet (FAC) 900
Installation Manual
_________________________________________________________
Specifications
Specifications for the Clearfield FAC 900 cabinet follow:
Dimensions
Base cabinet
36” H x 23” W x 48” D
Expansion Module (EXM)
36” H x 24” W x 29” D
Riser options (for base cabinet and/or EXM)
6” H or 12” H (riser only)
Weight
Standard configuration (base cabinet with equipment shelves,
protection blocks and frames, and an internal battery enclosure)
290 lbs
Expansion Module
50 lbs
Internal battery enclosure
25 lbs
Battery string (100Ah)
315 lbs
Enclosure Mounting
Concrete pad
Clearfield cast-in-place template
Pre-cast concrete pad
Third-party supplied
Foundation vault
Third-party supplied
Wall/H-frame
Clearfield wall/H-frame mounting kit option
Equipment Mounting
Equipment mounting space
19 inches (8RU); 8RU mounting space for Clearfield service units or third-party equipment
Rack attributes
19-inch EIA standard; oriented for vertical mounting
Environmental
Heat exchanger
Door mounted Internal fan Tmin = 30C (50% RPM) and Thigh = 45C (100% RPM)
External fan Tstop = 30C, Tmin = 40C (50% RPM) and Thigh = 55C (100% RPM)
Cooling capacity
47 Watts/°C
Thermal operating range
-40C to +46C
Environmental alarming
Environmental
Electrical (Local Power)
AC load center
208-240 VAC load center
Duplex convenience outlet (GFCI protected)
AC junction box (option)
120/240 VAC junction box (2 inputs/2 outputs)
Duplex convenience outlet (GFCI protected
Generator connector (option)
30 Amp NEMA twist-lock (Hubbell)
DC power system
Alpha non-LVD Cordex 1.2HP 1RU Shelf; (3) 1200W (25A) rectifier modules; fuse protected
DC Distribution (28 position)
Battery backup
Support for (1) string of front post VRLA or Saft Tel100 Ni-Cd 100Ah batteries [up to (2) 100Ah
strings with optional EXM]; battery heater option available for VRLA battery string
Cable Entrance
Outside plant entry
(1) square feed through accommodating (2) 4.5-inch conduits
AC service entry (local power only)
(1) 2.5-inch diameter entry port
Compliance
Safety
UL 67
EMC
FCC Part 15, Class A
Telcordia
GR-487-CORE, Issue 2