OL-32062-01
Chapter 3 Maintaining the System
Installing or Replacing System Components
Identifying a Faulty Internal Drive
The system has internal-drive fault LEDs on the right-front handle (see
Figure 3-1
). Use these LEDs to
get an indication of the location of a failing drive.
Step 1
Observe the internal-drive fault LEDs on the right-front handle.
•
The two columns of LEDs correspond to the two halves of the internal drive compartment (under
either the right- or left-side top cover).
•
The four numbered rows of LEDs correspond to the four horizontal rows of drive bays (14 drive bays
in each row).
See
Figure 3-9
for an example. In this example, the amber LED indicates that the failing drive is in the
right half of the internal drive compartment, in row 3.
Step 2
Open the right- or left-side cover and look at the fault LEDs on the drive trays.
A solid amber fault LED indicates a failed drive.