Switch Power Input Requirements
The following table lists the typical amount of power that the switch consumes. It also lists the maximum
amount of power that you must provision for the switch and power supply for peak conditions.
Some power supplies have UL listed capabilities that are greater than the maximum power requirements for
a switch. To determine the power consumption characteristics for the switch, use the typical and maximum
requirements that are listed in the following table.
Note
Heat Dissipation
Requirement
Maximum Power
Consumption (AC or DC)
Typical Power
Consumption (AC or DC)
Switch
1552.524 BTUs per hour
455 W
232 W
Cisco Nexus 9396PX
Power Specifications
Power specifications include the specifications for each type of power supply module.
650-W AC Power Supply Specifications
These specifications apply to the following power supplies:
• N9K-PAC-650W
• N9K-PAC-650W-B
Specification
Characteristic
Nominal range: 100 and 240 VAC (Range: 90-132
VAC, 180-264 VAC)
AC input voltage
Nominal range: 50 to 60 Hz (Range: 47-63 Hz)
AC input frequency
7.6 A at 100 VAC
3.65 A at 208 VAC
Maximum AC input current
760 A at 100 VAC
Maximum input volt-amperes
650 W
Maximum output power per power supply
33 A (sub-cycle duration)
Maximum inrush current
12 ms at 650 W
Maximum hold-up time
12 VDC
Power supply output voltage
12 VDC
Power supply standby voltage
Cisco Nexus 9396PX ACI-Mode Switch Hardware Installation Guide
49
System Specifications
Switch Power Input Requirements