the adjacent wiring box. This allows wiring multiple units to the same circuit with only a single supply
wire entry point.
When combining multiple switches on a single circuit, refer to the switch ampacity tables
below to verify that the number of switches is appropriate, given the circuit
’
s voltage and
ampacity. The switch ampacity table provides number of units that fit on a single circuit
(after derating to 80% of capacity), i.e. 15A circuit gives number of units possible when only
12A (80% of 15A) is used.
Table 2: Switch Ampacity Rating for Catalyst Digital Building Series PoE/PoE+ Switch
Warning
30A
20A
15A
Circuit
Breaker
Rating:
CDB-8P
24A
16A
12A
Circuit
Breaker
Derating
(80%):
Maximum
Current
Consumption
Nominal
Input
Voltage
9
6
4
Units /
Circuit
2.68A
115VAC
18
12
9
Units /
Circuit
1.34A
230VAC
21
14
10
Units /
Circuit
1.16A
277VAC
Table 3: Switch Ampacity Rating for Catalyst Digital Building Series UPOE Switch
30A
20A
15A
Circuit
Breaker
Rating:
CDB-8U
24A
16A
12A
Circuit
Breaker
Derating
(80%):
Maximum
Current
Consumption
Nominal
Input
Voltage
4
3
2
Units /
Circuit
5.18A
115VAC
9
6
4
Units /
Circuit
2.59A
230VAC
11
7
5
Units /
Circuit
2.18A
277VAC
Catalyst Digital Building Series Switch Hardware Installation Guide
64
Switch Installation
Flexible Mounting
Содержание CDB-8P
Страница 56: ...Catalyst Digital Building Series Switch Hardware Installation Guide 46 Switch Installation Flexible Mounting ...
Страница 64: ...Catalyst Digital Building Series Switch Hardware Installation Guide 54 Switch Installation Flexible Mounting ...
Страница 70: ...Catalyst Digital Building Series Switch Hardware Installation Guide 60 Switch Installation Flexible Mounting ...
Страница 79: ...Catalyst Digital Building Series Switch Hardware Installation Guide 69 Switch Installation Rack Mounting ...
Страница 81: ...Catalyst Digital Building Series Switch Hardware Installation Guide 71 Switch Installation Rack Mounting ...