11-11
Cisco BPX 8600 Series Installation and Configuration
Release 9.3.30, Part Number 78-12907-01 Rev. E0, May 2005
Chapter 11 Installing the AC Shelf
Card Slot Fuses
Note
The BPX switch circuit breaker is 20 A to provide improved system availability for
installations with a single line cord and (N+1) power supplies.
Step 3
For the dual power feed version, plug each power cord into receptacles on separate building circuits to
provide protection against a power feed failure. Each building circuit should be protected with a 20 A
circuit breaker.
Step 4
The ground (green/yellow) wire of the AC power cord provides the safety ground to the BPX switch via
the grounding prong on the three-prong connectors. Make sure the building AC receptacle is also
properly grounded as shown in Figure 11-10.
Figure 11-10 AC Power
Step 5
As applicable, provide a convenience AC outlet strip, with at least four outlets, near the BPX switch to
power optional modems, CSU, or DSU, test equipment, and so forth. There is no accessory AC outlet
supplied on the BPX switch. The outlet strip should be connected to a source of AC voltage normal for
the region (such as, 115 VAC for domestic US use).
Step 6
Proceed to Chapter 13, “Installing the BPX Switch Cards.”
Card Slot Fuses
Fuses for each card slot on the backplane of the BPX switch protect against catastrophic backplane
damage in the event of a shorted connector power pin. The card slot fuses are designated F4 through F18,
corresponding to card slot numbers 1 through 15, respectively.
Backplane fuses should rarely, if ever, need replacement.
For instructions on replacement of these fuses, see Chapter 29, “Replacing Parts.” Contact Cisco
Customer Service for assistance regarding their replacement.
Caution
For continued protection against risk of fire, replace only with the same type and rating of fuse. Fuses
should be replaced only after all power to the BPX switch has been turned off.
L1
180 - 240 VAC
L2
H10038
Содержание BPX 8650
Страница 49: ...P A R T 1 The BPX Switch ...
Страница 50: ......
Страница 159: ...P A R T 2 Installation ...
Страница 160: ......
Страница 273: ...P A R T 3 Initial Configuration and Network Management ...
Страница 274: ......
Страница 311: ...P A R T 4 Configuring Connections ...
Страница 312: ......
Страница 487: ...P A R T 5 Troubleshooting and Maintenance ...
Страница 488: ......
Страница 533: ...P A R T 6 BPX Specifications ...
Страница 534: ......
Страница 555: ...P A R T 7 Appendices ...
Страница 556: ......