68
SVGm
Instruction Manual
8�2�2�2�- Mains Measurements
Table 25: Modbus memory map: Measurements in the Mains�
Parameter
L1
L2
L3
LN
Units
Current in Mains
9B - 9A
9D - 9C
9F - 9E
A1 - A0
[Hi] + [Low] A with 1 decimal
Active power in Mains
BF - C0
C1 - C2
C3 - C4
-
kW with 2 decimal places and sign.
Reactive power in Mains
C5 - C6
C7 - C8
C9 - CA
-
kVar with 2 decimal places and sign.
Apparent power in Mains
CB - CC
CD - CE
CF - D0
-
kVA with 2 decimal places and sign.
cos
ɸ
in Mains
D4
D5
D6
-
With 3 decimal
Mains frequency
D7
-
Hz with 1 decimal
8�2�2�3�- Other parameters of the SVGm static generator
Table 26: Modbus memory map: Static generator parameters (Table 1)�
Parameter
Address
Units
Temperature IGBT 1
(1)
DB
ºC with 1 decimal
Temperature IGBT 2
(1)
DC
ºC with 1 decimal
Temperature IGBT 3
(1)
DD
ºC with 1 decimal
Temperature Inductor 1
(1)
E7
ºC with 1 decimal
Temperature Inductor 2
(1)
E8
ºC with 1 decimal
Temperature IGBT 4
(1) (2)
F5
ºC with 1 decimal
Temperature IGBT 5
(1) (2)
F6
ºC with 1 decimal
Temperature IGBT 6
(1) (2)
F7
ºC with 1 decimal
Temperature Inductor 3
(1) (2)
FB
ºC with 1 decimal
Temperature Inductor 4
(1) (2)
FC
ºC with 1 decimal
Phase L1 - L2 voltage
DE
V with 1 decimal
Phase L2 - L3 voltage
DF
V with 1 decimal
Phase L3 - L1 voltage
E0
V with 1 decimal
Positive DC bus voltage
E1
V with 1 decimal
Negative DC bus voltage
E2
V with 1 decimal
(1)
For a system with devices in parallel, the parameter value is that of the device connected with RS-485.
(2)
Parameters only accessible for the 60 kvar model.
Table 27: Modbus memory map: Static generator parameters (Table 2)�
Parameter
L1
L2
L3
LN
Units
Current in the static generator
A3 - A2
A5 - A4
A7 - A6
A9 - A8
[Hi] + [Low] A with 1 decimal
Phase – neutral voltage
AA
AB
AC
-
V with 1 decimal
% of static generator power used
D8
D9
DA
-
%
Table 28:Modbus memory map: Static generator parameters (Table 3)�
Parameter
Address
Description
SVGm
serial no.
(3)
2710 - 2711
Hi [10] + Low [11] serial no.
DSP software version
10C
-
HMI software version
1C3
-
(3)
For a system with devices in parallel, the parameter value is that of the device connected with RS-485.
Содержание SVGm-3WF-100C-480
Страница 1: ...SVGm M248B01 03 21A Static var generator INSTRUCTION MANUAL ...
Страница 2: ...2 SVGm Instruction Manual ...
Страница 98: ...98 SVGm Instruction Manual 14 CE CERTIFICATE ...
Страница 99: ...99 Instruction Manual SVGm ...
Страница 100: ...100 SVGm Instruction Manual ...
Страница 101: ...101 Instruction Manual SVGm ...