83
Instruction Manual
SVGm
9
Figure 85: SVGm type Rack Change of cooling fans (Step 9)�
10
Remove the fan assembly by pulling it up, and replace it with the new fans.
10
Figure 86: SVGm type Rack Change of cooling fans (Step 10)�
11
Tighten the fan assembly screws.
4
5�5 Nm
12
Mount the bars. Tighten the IGBT and inductance screws.
IGBT screws :
4�5 Nm
Inductance screws :
8 Nm
13
Mount the driver board. Use the visual guides. The cross should be seen through the holes in the
board.
14
Screw the driver board.
0�7 Nm
15
Place the wall bushing on the bar brackets and reassemble the board bracket. Screw in.
4�5 Nm
16
Connect the flat belts, Hall-effect sensors and fans.