16
SVGm
Instruction Manual
It should be noted that, depending on the installation conditions in the cabinet and in the room where
this is placed, the outflows of hot air may be sucked back in by the device’s fans, causing a feedback
of hot air that will lower the performance of the device.
It is also necessary to bear in mind the power dissipated by the device when choosing where to install
it, to ensure proper air recirculation, to make sure that the intake air is a suitable temperature. See
“
Table 10: Ventilation distances: Rack-type SVGm
�
Ventilation distances: Rack-type SVGm
300 mm
300 mm
3�2�1�3�- Cabinet-type SVGm
The cabinet-type
SVGm
uses a forced ventilation cooling system, with an air inlet on the front panel
and an air outlet at the back of the device.
The ventilation grille at the top must not be blocked, leaving enough space to the ceiling to allow the
heat to dissipate. The distance depends on the characteristics of the installation site.
There is no need to leave space between the sides or at the back of the cabinet; they can be installed
next to other cabinets and against a wall.
Table 11: Ventilation distances: Cabinet-type SVGm�
Ventilation distances: Cabinet-type SVGm
300 mm
Table 12: Air flow depending on the models�
Model
Power
(kvar)
air flow
SVGm-3WF-100C-480
100
375 m
3
/h
SVGm-4WF-069C-400
69
SVGm-3WF-100C-690
100
425 m
3
/h
SVGm-4WF-067C-550
67
Содержание SVGm-3WF-100C-480
Страница 1: ...SVGm M248B01 03 21A Static var generator INSTRUCTION MANUAL ...
Страница 2: ...2 SVGm Instruction Manual ...
Страница 98: ...98 SVGm Instruction Manual 14 CE CERTIFICATE ...
Страница 99: ...99 Instruction Manual SVGm ...
Страница 100: ...100 SVGm Instruction Manual ...
Страница 101: ...101 Instruction Manual SVGm ...