19
Instruction Manual
SVGm
Fit the device with the help of another person.
4�-
Fasten the device to the points provided for this purpose. Use
4
M6
fixing screws.
3�4�3�- CABINET-TYPE SVGm
The Cabinet-type
SVGm
models are free-standing cabinets with 4 bearing supports on the floor.
The mounting surface must be solid, support the device’s weight and be level.
The cabinet must never be welded to the floor using arc welding, as this may destroy
the electronic components.
The device’s top panel is part of the ventilation system. The top panel is inverted to make it easier to
transport.
It must be placed in the correct position to enable the device to operate properly. To do this:
1�-
Remove the transport rings.
2�-
Remove the top panel from the top of the cabinet.
3�-
Rotate the top panel. The non-slotted part goes at the front of the cabinet.
4�-
Install the transport rings with rubber washers supplied.
20 Nm
Figure 6: Top panel of an SVGm cabinet�