44
RGU-100B
Instruction Manual
8�2�- WGB
Electrical features
Models
WGB-35
WGB-55
WGB-80
WGB-110
Type
Bar
Maximum rated current of the monitored circuit
(In)
80 A
160 A
250 A
400 A
Frequency
50... 1 kHz
Maximum operating voltage
≤ 720 V ~, ≤ 750 V
Accuracy
Tripping current
30 mA
± 2 mA
100 mA
± 5 mA
300 mA
± 20 mA
500 mA
1�0 A
± 200 mA
3�0 A
User interface
LED
6 LEDs
Environmental features
Operating temperature
-10 ºC ... +50 ºC
Storage temperature
-20 ºC ... +70 ºC
Relative humidity (without condensation)
5... 95%
Maximum altitude
2000 m
Thermical class
150 ºC
Mechanical features
WGB-35
WGB-55
WGB-80
WGB-110
Window size
Ø
35.5 mm
Ø
55.5 mm
Ø
80.5 mm
Ø
110.5 mm
Weight
235 g.
355 g.
555 g.
750 g.
Enclosure
Self-extinguishing V0 plastic
Cable from WGB to RGU-100B
Connector
RJ45 standard
Cable cross-section
4 x 2 x AWG24/7
Temperature range
-20 ºC ... +70 ºC
Length
(8)
1.5 m
(8)
Length of the cable included with the
WGB
.
Standards
Low-voltage switchgear and controlgear - Part 2: Circuit-breakers
IEC 60947-2-M
Содержание RGU-100B