36
RGU-100B
Instruction Manual
7�3�- MODBUS COMMANDS
All
MODBUS
map addresses are in Hexadecimal format.
7�3�1�- VARIABLES OF THE RGU-100B AND INSTALLATION
Function 0x02
is used for these variables.
Functions
0x01
and
0x05
are used for the variable
Save the new installation
.
Table 10: Modbus Memory Map: RGU-100B - INSTALLATION (Table 1)�
RGU-100B - INSTALLATION
Parameter
Format
Address
Value
Installation tripped due to
TRIP
input
bool
5DC
0:
Not tripped -
1:
Tripped
The installation has changed
bool
7CE
0:
Not changed -
1:
Changed
Internal error detected in the
RGU-100B
bool
7CF
0:
Not detected -
1:
Detected
Save the new installation
bool
F9F
1:
Save the installation
Function 0x04
is used for these variables.
Table 11: Modbus Memory Map: RGU-100B - INSTALLATION (Table 2)�
RGU-100B - INSTALLATION
Parameter
Format
Address
Value
Date and time of the device
Unit [32]
283C - 283D
Device date
(Epoch format)
Serial no. of the
WGB
registered in the installation's
Channel
String
3458 ...345E
-
Installation status
Unit [16]
3583
0��� 5
)
Status of
RGU-100B
Unit [16]
3584
0��� 2
)
ID no. of
RGU-100B
Unit [32]
35E8-35E9
-
Serial no. of
RGU-100B
Unit [16]
364C... 3652
-
Possible installation statuses,
:
Table 12: Installation statuses�
Possible installation statuses
Value
Description
0
Correct installation
1
A new
WGB
has been detected and added to the installation
2
The
WGB
registered in the installation is not detected
3
A
WGB
not registered in the installation has been detected
4
More WGB's than the installation can accept has been detected
5
There is no
WGB
registered in the installation
Possible statuses of
RGU-100B
Содержание RGU-100B
Страница 1: ...INSTRUCTION MANUAL Protection and monitoring relay RGU 100B M256B01 03 20A...
Страница 2: ...2 RGU 100B Instruction Manual...
Страница 47: ...47 Instruction Manual RGU 100B 11 CE CERTIFICATE...
Страница 48: ...48 RGU 100B Instruction Manual...
Страница 49: ...49 Instruction Manual RGU 100B...
Страница 53: ...53 Instruction Manual RGU 100B...