30
RGU-100B
Instruction Manual
Figure 28: Password Screen�
Use keys
and
to modify the digit's value.
Press key
keys to skip the digit.
To validate the value, hold down the key
for > 3s; if the password is correct, in the bottom left of
the display, we can see the icon
.
Note:
The password can be modified in
If the password is not entered or the one entered is incorrect, in the bottom left of the display, we can
see the icon
, and only the clock setup menu can be modified. Some of the other menus will be
visible and others not.
6�1�- RS-485 COMMUNICATIONS
shows the initial screen of the RS-485 communications menu. Press the key
for > 3s,
to access the menu.
Figure 29: Communications menu�
6�1�1�-BAUD RATE
In this screen, the baud rate of the RS-485 communications is set up.
Use keys
and
to skip through the different options:
4.8
(4800),
9.6
(9600),
19.2
(19200),
38.4
(38400),
57.6
(57600),
115.2
(115200)
bps
To skip to the next programming point, press once the key
.
Hold down the key
for > 3s, to validate the data and exit the programming.