5�3�- TARGET COS
φ
The cos
φ
makes it possible to define the power factor required for the installation. The
Computer
SMART III FAST
will add the number of capacitors needed to adjust the value as close as possible
to the objective value. Since the regulation is by stages, it does not perform any operations until the
uncompensated demand is at least 70 % of the power of the smallest stage or the compensation
surplus is 70 % of the power of the smallest stage.
Four target cosines can be configured, depending on the status of the digital inputs (
See
)
the unit allows one of the 4 programmed cosines.
For every cosine, you must program the value and state whether it is inductive
L
or capacitive
C
.
Press the
key to enter editing mode. It is identified by the
symbol and the blinking of the
digits to be modified.
The
key increases the digit value or shows the next option.
The
key decreases the digit value or shows the next option.
The
key skips to the previous digit and the
key skips to the next digit.
Press
to validate the data; the
symbol disappears from the display.
Maximum value:
1.00.
Minimum value:
0.50.
If the value entered is lower than the minimum value or higher than the maximum value, the backlight
of the display flashes and the value entered is replaced with the minimum or maximum value, or with
the last value validated.
Press key
to access the next programming step.
If no keys are pressed for 5 minutes, the unit switches to the simulation screen,
.
73
Instruction Manual
Computer SMART III FAST
Содержание Computer SMART III FAST 12
Страница 1: ...INSTRUCTION MANUAL M021B01 03 21A REACTIVE ENERGY REGULATOR Computer SMART III FAST Static operation...
Страница 2: ...2 Computer SMART III FAST Instruction Manual...
Страница 108: ...9 CE CERTIFICATE 108 Computer SMART III FAST Instruction Manual...
Страница 109: ...109 Instruction Manual Computer SMART III FAST...
Страница 110: ...110 Computer SMART III FAST Instruction Manual...
Страница 111: ...111 Instruction Manual Computer SMART III FAST...