5.- CONFIGURATION
The various configuration parameters of the unit can be consulted and edited in the unit setup menu.
The unit always keeps the capacitors disconnected (except in the Plug&Play function).
This status is identified by the
symbol in the unit status area of the display (
To access the setup menu, press and hold the
key (> 3 s).
The Password screen appears on the display.
The password to be entered is a combination of keys:
. It is unique and cannot
be configured.
If it is not entered correctly, the unit returns to the previous measurement screen.
If it is entered correctly and capacitors are connected, the disconnection screen appears.
Disconnection screen: used for the unit to automatically disconnect all the stages before entering into
configuration.
While in this screen, the unit does not respond to the keys.
The unit automatically exits this screen, and this can take a certain amount of time.
68
Computer SMART III FAST
Instruction Manual
Содержание Computer SMART III FAST 12
Страница 1: ...INSTRUCTION MANUAL M021B01 03 21A REACTIVE ENERGY REGULATOR Computer SMART III FAST Static operation...
Страница 2: ...2 Computer SMART III FAST Instruction Manual...
Страница 108: ...9 CE CERTIFICATE 108 Computer SMART III FAST Instruction Manual...
Страница 109: ...109 Instruction Manual Computer SMART III FAST...
Страница 110: ...110 Computer SMART III FAST Instruction Manual...
Страница 111: ...111 Instruction Manual Computer SMART III FAST...