Press the
key to access the next programming step.
If no keys are pressed for 5 minutes, the unit switches to the simulation screen,
.
5�24�- COS
φ
HIGH ALARM
The high limit of the cos
φ
alarm is set at this point. This is activated whenever the value of cos
φ
is
above the specified value and the current is higher than the programmed value.
Note:
The alarm must be enabled
(
).
Press the
key to enter edit mode. It is identified by the
symbol and the flashing of the
digits to be modified.
In order to avoid possible false activations of said alarms, they have a predefined delay of 15 seconds.
The
current value�
The
cos
φ
value
,
it is capacitive
C
.
The
key increases the digit value or shows the next option.
The
key reduces the digit value or shows the next option.
The
key skips to the previous digit and the
key skips to the next digit.
Press
to validate the data; the
symbol disappears from the display.
Current:
Maximum value:
9999 A
Minimum value:
0 A
cos
φ
:
Maximum value:
1.00
Minimum value:
0.50
If the value entered is lower than the minimum value or higher than the maximum value, the backlight
of the display flashes and the value entered is replaced with the minimum or maximum value, or with
the last value validated.
96
Computer SMART III FAST
Instruction Manual
Содержание Computer SMART III FAST 12
Страница 1: ...INSTRUCTION MANUAL M021B01 03 21A REACTIVE ENERGY REGULATOR Computer SMART III FAST Static operation...
Страница 2: ...2 Computer SMART III FAST Instruction Manual...
Страница 108: ...9 CE CERTIFICATE 108 Computer SMART III FAST Instruction Manual...
Страница 109: ...109 Instruction Manual Computer SMART III FAST...
Страница 110: ...110 Computer SMART III FAST Instruction Manual...
Страница 111: ...111 Instruction Manual Computer SMART III FAST...