The
Lo
value:
when the unit exceeds this value for 30 minutes, alarm
E09
is triggered, and
if alarm
E11
is enabled
,
the
Computer SMART III FAST
unit enters
No Connection
status and
activates
alarm
E11
.
The
HI
value:
if the unit exceeds this value for 30 seconds, alarm
E09
is triggered, and if
alarm
E12
is enabled, the
Computer SMART III FAST
unit enters the
Disconnection
status and
activates
alarm
E12
.
If the unit falls back under the
Lo
value for 10 minutes, it deactivates the alarms and returns to the
normal operating status.
In the
No Connection
status, the unit does not connect the stages, but also does not disconnect them
if the operation requires it.
In the
Disconnection
status, it disconnects all the stages and does not allow them to connect.
The
key increases the digit value.
The
key decreases the digit value.
The
key skips to the previous digit and the
key skips to the next digit.
Press
to validate the data; the
symbol disappears from the display.
Lo
Value
and
HI
Value:
Maximum value:
9999.
Minimum value:
1
If the value entered is lower than the minimum value or higher than the maximum value, the backlight
of the display flashes and the value entered is replaced with the minimum or maximum value, or with
the last value validated.
Press the
key to access the next programming step.
If no keys are pressed for 5 minutes, the unit switches to the simulation screen,
.
99
Instruction Manual
Computer SMART III FAST
Содержание Computer SMART III FAST 12
Страница 1: ...INSTRUCTION MANUAL M021B01 03 21A REACTIVE ENERGY REGULATOR Computer SMART III FAST Static operation...
Страница 2: ...2 Computer SMART III FAST Instruction Manual...
Страница 108: ...9 CE CERTIFICATE 108 Computer SMART III FAST Instruction Manual...
Страница 109: ...109 Instruction Manual Computer SMART III FAST...
Страница 110: ...110 Computer SMART III FAST Instruction Manual...
Страница 111: ...111 Instruction Manual Computer SMART III FAST...