![CIAT CLIMACIAT MAST'AIR Скачать руководство пользователя страница 24](http://html1.mh-extra.com/html/ciat/climaciat-mastair/climaciat-mastair_installation-operation-commissioning-maintenance_2606752024.webp)
EN - 2
INSTALLATION
1. DELIVERY
General Delivery Conditions
Equipment receipt assumes the availability of the lifting and handling facilities and aids required as appropriate to size and weight
(see “handling” section).
Check the equipment condition on arrival. In the event of any damage, note the reservations on the delivery docket and confirm
to the carrier by registered mail within the three days following delivery.
Delivery method
Freestanding and of bolted construction, the units are delivered either:
•
In sections ready for assembly. Assembly accessories (seals, bolts, flexible sealing cement) are delivered in the packages
together with the unit components.
•
Or as single or dual units.
2. HANDLING
CIAT air handling units
CIAT air handling units must be handled as detailed by the following diagram.
General precautions
Never attach a sling on to couplings, flanges, tubes, access handles, hinges, suction apertures.
Never carry out any handling operations that could cause damage to internal components (turning the unit onto its side, etc.)
without having first removed these components.
Where possible, always place a wooden shim between the unit and levers, scaling bars, and other lifting devices so as to avoid
damaging the unit’s finish and sealing.
Failure to respect the above rules will result in CIAT’s guarantee becoming null and void.
CIAT air handling units
CIAT air handling units are fitted with lifting lugs (depending on size). Units must only be lifted by overhead gantry or crane using
the lifting lugs fitted to their lower surface. These lugs can be removed after the units have been positioned.
Each section is fitted with top and bottom rails. The bottom rails are fitted with lifting lugs marked CE.
Assembling the sections together: A coupling frame is factory fitted to one of the sections. Fasten the following section to this frame.
Fasten the vertical members of the section to the frame via the outside and the horizontal members of the frame via the inside.
Threaded rods between the top rails and the bottom rails ensure that the sections are correctly sealed and aligned with each other.