Control Setup
Chore-Tronics® 3 Control
60
MT2398C
Cool Setting
1. Select the Main menu button.
Select the Ventilation Settings button.
2. Select the Cool button.
3.
Cool Outputs
Disabled Above RH-
If there are
relays assigned to cool output(s), and a relative hu-
midity sensor is connected to the Control, the Con-
trol can block the cool output from turning on if the
relative humidity sensor reading is higher than en-
tered value.
4.
Allow Cool From
- User can also specify a specific time of day in which the cool outputs
are allowed to operate. A setting of 12:00a to 12:00a means that the cool outputs are allowed
to operated 24 hours per day.
5.
Do Not Allow Cool To Go Below
- Outputs
can have a minimum temperature setting. If the
cool or Cool Pad outputs reach this minimum
temperature due to the set temperature changing
the outputs will not go below this minimum tem-
perature even though the set temperature may
continue to lower due to the set temperature
curve.
3
4
5
Содержание Chore-Tronics 3 Control
Страница 1: ...Chore Tronics 3 Control Installation Operator s Instruction Manual MT2398C November 2013...
Страница 124: ...Wiring Diagrams Chore Tronics 3 Control 124 MT2398C Fan Wiring Figure 45 Fan Wiring...
Страница 127: ...Chore Tronics 3 Control Wiring Diagrams MT2398C 127 This page left blank intentionally...
Страница 128: ...Wiring Diagrams Chore Tronics 3 Control 128 MT2398C Brooder Wiring...
Страница 129: ...Chore Tronics 3 Control Wiring Diagrams MT2398C 129...
Страница 133: ...Chore Tronics 3 Control Improving Lightning Surge Suppression MT2398C 133 This page left blank intentionally...
Страница 141: ...Chore Tronics 3 Control Technical Specifications MT2398C 141 This page left blank intentionally...