Control Setup
Chore-Tronics® 3 Control
47
MT2398C
Tunnel Inlet
1. Use the Back button to get to the Setup/Out-
puts screen and push the Tunnel Inlet Button.
2. When you enter in the Open relay number
the Control will automatically enter the Close
relay.
Up to four machines can be assigned to the
Tunnel inlet output. All machines will be giv-
en an open or close signal at the same time.
Note. The Open and Close outputs must al-
ways be side by side on the same relay row.
Open Relay Number
3. Press the Control Tab
4. These numbers are needed for proper
Mode transitions. (Power to Tunnel and
Tunnel to Power).
Full Movement
Measure the full movement of the Curtain or
Tunnel door and enter that number in the FULL
Movement edit box.
Tunnel Speed
With a closed inlet measure 18 inches of the tun-
nel curtain or door movement. Toggle the open
relay switch to the Manual position.
Time how long it takes to move the the Inlet 18
inches. Enter that number in to the Tunnel
Speed edit box
.
Содержание Chore-Tronics 3 Control
Страница 1: ...Chore Tronics 3 Control Installation Operator s Instruction Manual MT2398C November 2013...
Страница 124: ...Wiring Diagrams Chore Tronics 3 Control 124 MT2398C Fan Wiring Figure 45 Fan Wiring...
Страница 127: ...Chore Tronics 3 Control Wiring Diagrams MT2398C 127 This page left blank intentionally...
Страница 128: ...Wiring Diagrams Chore Tronics 3 Control 128 MT2398C Brooder Wiring...
Страница 129: ...Chore Tronics 3 Control Wiring Diagrams MT2398C 129...
Страница 133: ...Chore Tronics 3 Control Improving Lightning Surge Suppression MT2398C 133 This page left blank intentionally...
Страница 141: ...Chore Tronics 3 Control Technical Specifications MT2398C 141 This page left blank intentionally...