Problem
Possible Cause
Possible Solution
Tunnel Curtain opens in Power
Mode.
A.) Power-Tunnel Mode Transi-
tion.
B.) High static pressure alarm
safety feature has taken over.
C.) Additional inlet area through
the Tunnel Curtain feature has
taken over.
A.) Normal Operation
B.) Static pressure had quickly
built to above 0.20” and
stayed there for over the wind
delay setting. Tunnel Curtain
will open to maintain a static
pressure of between 0.18 and
0.20.” This is usually accom-
panied by a high static pres-
sure alarm. Find cause of
high static pressure and cor-
rect.
C.) Normal operation. Whenever
the air Inlets do not provide
enough air, the Tunnel Cur-
tain will also open enough to
maintain static pressure
within the Power Mode lim-
its.
When half-house brooding the
Minimum Rel. alarm is continu-
ally going off. The Sensor(s) indi-
cated are always in the non-brood
end.
One or more non-brood end Sen-
sors are assigned as Mode Sensors
and/or there are non-brood sen-
sors assigned to the power mode
sensors in the Alarms Screen.
Remove non-brood Sensor(s) as
Mode Sensors when brooding.
Sensor(s) can still be assigned to
heaters, etc. to keep non-brood
end temperature above freezing.
It is a cool-breezy day, and when
the Control goes into Natural
Mode the Curtains open to the
first opening position (example:
12 inches on a 48-inch Curtain).
After about 30 seconds the Con-
trol goes back into Power Mode
and the Curtains close right back
up. It does this several times.
Normal Operation
If the temperature drops .6× F in
the first two minutes, the Curtains
are given a continuous close sig-
nal and the Control goes back into
Power Mode. This is the quick
temperature check as described in
the Mode Transitions, "
Power to
Natural
", section of this Manual.
Troubleshooting
Chore-Tronics® 3 Control
116
MT2398C
Programming Trouble Shooting Continued.....
Equipment and Potentiometer Troubleshooting
Problem
Possible Cause
Possible Solution
Display difficult to read.
A.) Back light on display board
unplugged or defective.
A). Check two wire plug on Dis-
play board. Replace if defec-
tive.
Display Completely Blank.
A.) Flat cable(s) between KB
board and Display board is
unplugged or defective.
B.) Defective Display board.
C.) Defective HI board.
D.) Defective KB Board
A). Check flat cable connections.
Replace cable if defective.
B). Replace Display Board.
C). Replace KD Board.
D.)Replace KB Board
The Control says that the pressure
in the house is .00" and will not
move.
There is a wire connection prob-
lem between the static pressure
monitor and the IO board. When
the static pressure monitor is dis-
connected from the IO Board the
Control defaults to a reading of
.00"
Check for wires being switched,
broken wires, wires not making a
good connection, etc. An easy
way to remember the wiring is
that the red wire is connected to
the positive terminal of both the
IO board and the static pressure
monitor.
Содержание Chore-Tronics 3 Control
Страница 1: ...Chore Tronics 3 Control Installation Operator s Instruction Manual MT2398C November 2013...
Страница 124: ...Wiring Diagrams Chore Tronics 3 Control 124 MT2398C Fan Wiring Figure 45 Fan Wiring...
Страница 127: ...Chore Tronics 3 Control Wiring Diagrams MT2398C 127 This page left blank intentionally...
Страница 128: ...Wiring Diagrams Chore Tronics 3 Control 128 MT2398C Brooder Wiring...
Страница 129: ...Chore Tronics 3 Control Wiring Diagrams MT2398C 129...
Страница 133: ...Chore Tronics 3 Control Improving Lightning Surge Suppression MT2398C 133 This page left blank intentionally...
Страница 141: ...Chore Tronics 3 Control Technical Specifications MT2398C 141 This page left blank intentionally...