Control Setup
Chore-Tronics® 3 Control
43
MT2398C
Ventilation-Cool Pad
The COOL PAD output is very different from a COOL output. It is not intended that the COOL PAD
output and the COOL output would be used together, but it is possible. Both outputs are there to give the
user the choice on which type of output to use. The COOL PAD's relay operation is designed to begin the
cooling caused by the cooling pad by first adding 5 seconds of water to the pad every 5 minutes. If the
temperature is still with the "Cool Pad Range" after 4 doses of 5 seconds of water, the amount of water
added to the pad every 5 minutes remains the same. If the temperature is above or below the temperature
limits of the "Cool Pad Range", the amount of water "on" time each 5 minutes is increased or decreased
5 seconds. With the default settings the temperature is only checked every 20 minutes. If it is desired for
the temperature to be checked more often if a sudden large temperature change occurs, then values should
be entered in the "Extra aggressive if" lines (Items and , Figure ). For example, The Control is set to be
extra aggressive if 3.0 degrees above the upper limit of the COOL PAD range. Whenever the temperature
is more than 3.0 degrees above the upper limit of the COOL PAD range the Control will begin checking
the temperature every 5 minutes (every repetition rate) instead of every 20 minutes (every 4 repetition
rates) until the temperature returns to less than 3.0 degrees above the COOL PAD range. The default extra
aggressive settings are 3 degree.
1. Select the Ventilation button.
2. Select the Cool Pad button to assign the Cool Pad outputs.
3. Assign a Relay, Sensors and a
Mode value to the Cool Pads.
Содержание Chore-Tronics 3 Control
Страница 1: ...Chore Tronics 3 Control Installation Operator s Instruction Manual MT2398C November 2013...
Страница 124: ...Wiring Diagrams Chore Tronics 3 Control 124 MT2398C Fan Wiring Figure 45 Fan Wiring...
Страница 127: ...Chore Tronics 3 Control Wiring Diagrams MT2398C 127 This page left blank intentionally...
Страница 128: ...Wiring Diagrams Chore Tronics 3 Control 128 MT2398C Brooder Wiring...
Страница 129: ...Chore Tronics 3 Control Wiring Diagrams MT2398C 129...
Страница 133: ...Chore Tronics 3 Control Improving Lightning Surge Suppression MT2398C 133 This page left blank intentionally...
Страница 141: ...Chore Tronics 3 Control Technical Specifications MT2398C 141 This page left blank intentionally...