37
test type
: to choose the type of test: Burn-in, Early-Break, or Break at I-Limit.
Maximum output Current
: to set the maximum output current, from 0.2 to 5mA.
Maximum output Voltage
: to set the maximum output voltage. This can be useful to prevent handling errors. It make it possible
to entrust the instrument to less experienced users, for particular applications (telephony, aviation, etc.) in which it is important
not to exceed some maximum test voltage.
For example, if the maximum voltage is set to 750V, the measurement will be made at 500V for the 500V switch setting, and at a
maximum of 750V for all the other settings.
The adjustment range is from 40 to 10,000V (15,000 V for the C.A 6555).
5.4. AdjUStMENt of tHE tESt VoLtAGES
Always on the third SET-UP screen.
Adjustable Voltage 1, 2, and 3
: to set the values of the 3 adjustable test voltages.
The adjustment range is from 40 to 15000V.
DISPLAY
DISPLAY
Press the DISPLAY key to see
the following screen.
Step & Ramp Functions
Set Step Function 1
Set Step Function 2
Set Step Function 3
Set Ramp Function 1
Set Ramp Function 2
Set Ramp Function 3
Set Step function 1, 2, and 3
: in the case of a measurement with a stepped voltage, used to set the voltages and the durations
of the steps.
Pressing the
key opens the following screen:
Step
Voltage
Duration (m:s)
Step Function 1
1
2
3
4
5
50 V
100 V
150 V
200 V
250 V
0:10
0:10
0:10
0:10
0:10
1:40
Total Run Time (m:s)
Step & Ramp Functions
Step
Voltage
Duration (m:s)
Step Function 1
6
7
8
9
10
300 V
350 V
400 V
450 V
500 V
0:10
0:10
0:10
0:10
0:10
1:40
Total Run Time (m:s)
Step & Ramp Functions
Press the DISPLAY key to
see the rest of the screen.