32
4.4. dISPLAy kEy
This key is used to browse through the various accessible screens containing all information available before, during or after
the measurement. Depending on the measurement mode and the configuration chosen (CONFIG key), the screens are different.
4.5. GrAPH kEy
GRAPH
M
Ω
GRAPH
508 V
508 V
3.018 G
Ω
3.018 G
Ω
00:01:00
00:01:00
3050
3000
2950
2900
2850
V
510
500
490
480
470
0
1:00
2:00
3:00
4:00
At the end of each measurement, pressing the GRAPH key displays the curve of variation of the insulation resistance
versus time.
Insulation resistance axis.
Time axis.
Curve R(t), solid line.
Minimum and maximum values
of the voltage and the resistance
and time at the location of the
cursor.
Test voltage axis.
Curve V(t), dotted line.
This curve is plotted using samples recorded during the measurement.
The
keys are used to move along the curve to display the exact values of each sample.
The minimum and maximum values may be the same if the time scale of the graph is too short.
In the case of a measurement in U-RAMP or U-STEP mode, this gives:
G
Ω
GRAPH
497 V
497 V
3.045 G
Ω
3.045 G
Ω
00:00:25
00:00:25
10.0
7.5
5.0
2.5
0
V
1000
750
500
250
0
0
1:00
2:00
3:00
4:00
G
Ω
GRAPH
193 V
193 V
2.996 G
Ω
2.996 G
Ω
00:00:17
00:00:17
10.0
7.5
5.0
2.5
0
V
1000
750
500
250
0
0
1:00
2:00
3:00
4:00
It is possible to zoom.
CONFIG
Press the CONFIG key.
The
keys are used to modify the time scale of the graph.
The
keys are used to modify the resistance scale of the graph.