35
5. CoNfIGUrAtIoN (SEt-UP)
This function is used to change the configuration of the instrument by directly accessing the parameters to be modified.
MR
U-STEP
U-RAMP
U-VAR.
U-FIXED
OFF
SET-UP
SET-UP
Set the switch to SET-UP.
General Settings
Set Default Parameter
Buzzer
Power Down
Baud rate
Date
Time
Temperature Unit
1
On
38400
2011-05-25
9:41
Celsius
100213
1.0.00
Instrument Number
Firmware
To select and modify a parameter, use the
,
,
and
arrow keys.
To validate a modification, move the blinking cursor back to the left margin.
To exit without applying the last modification, turn the switch.
SET-UP
! WARNING !
O.K.
CANCEL
All parameters
will be reset !
If you accept by choosing OK, the following data will be modified:
The audible level of the buzzer returns to 1.
The automatic switching off of the instrument will occur at the end of 5 minutes.
The data rate will be 38400 bauds.
The duration of the measurements with programmed duration will be 2 minutes.
The sampling duration will be 10 seconds.
The DAR will be 30/60 and the PI 1/10.
The type of test will be Burn-in.
The maximum output current will be 5mA.
The maximum output voltage will be 10kV (15kV for the C.A. 6555).
The adjustable test voltages will be 50, 500 and 2500V.
The ramp and step test voltages return to their original values, as do all alarm thresholds.
5.1. rEStorING tHE INItIAL CoNfIGUrAtIoN
To return to the initial configuration, choose
Set default Parameter.
The instrument requests confirmation.
The following screen appears.