28
CONFIG
Press the DISPLAY
key to see the second
configuration screen.
DISPLAY
Test Type
I-Range
Disturbance Level
2500V
CONFIG
Burn-in
1 mA
Auto(2)
Low
< 2.5 M
Ω
Maximum Ouput Current
The
keys are used to select the
measurement configuration. The chosen
configuration is validated by pressing the
CONFIG key again.
FIXED VOLTAGE
1000 V
Input voltage
Frequency
Input current
Date 2011.05.23
10 V AC
50.0 Hz
24.6 pA
Time 10:31
E-BRK
500 V
2500 V
The second configuration screen depends on the setting of the switch.
The U-RAMP and U-STEP settings do not use the first page of the configuration screen, only the second.
The second configuration screen is used to choose:
The type of test (Test Type)
Nondestructive test (Early break)
The measurement will be stopped at the first breakdown current peak detected. This type of test is used for non-destructive
tests.
The E-BRK symbol is displayed.
CONFIG
Total Run Time
00:02:00
Manual Stop
Manual Stop + DD
Timed Run
(m:s)
2
:00
Timed Run + DD
DAR (s/s)
30/60
PI (m/m) 1.0/10
To do this, use the
and
keys.
The test will last the time programmed. However, if, during the measurement, the rotary switch is turned or the START/STOP
button is pressed, the measurement will be broken off.
When you select Timed Run (test with programmed duration) or Timed Run + DD, you can set the duration of the measurement
(m:s).