ACCESSORY WIRING
MISCELLANEOUS WIRING
THREE BUTTON CONTROL STATION
(4 Terminals)
•
OPEN and COM:
Opens a closed gate.
Hard open (maintained switch overrides external safeties and resets
alarm condition). If maintained, pauses Timer-to-Close at OPEN limit.
Opens a closing gate and holds open an open gate (within
line-of-sight).
•
CLOSE and COM:
Closes an open gate.
Hard close (maintained switch overrides external safeties and resets
alarm condition within line-of-sight)
•
STOP and COM:
Stops a moving gate.
Hard stop (maintained switch overrides Open and Close commands
and resets alarm condition). If maintained, pauses Timer-to-Close at
OPEN limit. Overrides Open and Close commands (within
line-of-sight).
FIRE DEPARTMENT OPEN INPUT
(2 Terminals)
Acts as hard open.
Maintained input overrides (ignores) external safeties (photoelectric
sensor and edge), pauses Timer-to-Close momentary input logic as single
button control and safeties remain active, re-enables Timer-to-Close.
ACCESSORY POWER 24 VDC, MAX 500 mA
(4 Terminals)
•
SWITCHED:
Switched ON with gate motion (stays on 5 seconds after
motion).
•
UNSWITCHED:
24 Vdc voltage out to power accessories, always ON.
Com
Open
(main control board)
Three Button Control Station
Fire Department
Com
Fire Dept
Acc Power +24 Vdc
Com (-)
(main control board)
Maglock
Solenoid Lock
(not provided)
(not provided)
(control board)
(control board)
Accessory Power Unswitched
Accessory Power Switched
Acc Power +24 Vdc
Com (-)
Close
Stop
N.C.
LOCKS
MAGLOCK
(2 Terminals, N.C. and COM)
Relay contact output, Normally - closed (N.C.) output for maglocks.
Relay activates prior to motor activation and during motor run. Relay is
off when motor is off.
SOLENOID
(2 Terminals, N.O. and COM)
Normally - open (N.O.) output for solenoid locks
Relay activates prior to motor activation and during motor run. Relay is
off when motor is off.
NOTE:
To conserve power for solar applications, the lock relay will only
activate for four seconds near the close limit.